| Number of channels per module |
1 configurable voltage or current outputs |
| Distribution of channels into groups |
1 group for 1 channel |
| Electrical isolation |
None |
| Connection of the signal AOU |
Terminal 11 |
| Connection of the signal AOI |
Terminal 10 |
| Power supply voltage |
Via the L+ and the M terminal of the processor module power supply |
| Output type |
Unipolar (voltage and current) |
| Resolution |
10 bits |
| Indication of the output signals |
Yes, one LED per channel |
| Output Resistance (load) as current output |
0 … 500 W |
| Output load ability as voltage output |
+2 mA max. |
| Accuracy for current and voltage output |
|
| Typical (25 °C) |
± 1 % of full-scale |
| Worst case (at 0 … 60 °C or EMC disturbances) |
± 2.5 % of full-scale |
| Relationship between input signal and hex code |
Onboard I/Os in Processor Module PM56x |
| Unused inputs |
Can be left open and should be configured as “unused” |
| Overvoltage protection |
Yes, up to 30 VDC |
| Max. cable length |
Conductor cross section > 0,14 mm² |
| |
Unshielded wire |
On request |
| |
Shielded wire |
100 m |