Measuring Ranges

Note

:strong:Risk of invalid analog input values!

The analog input values may be invalid if they exceed the measuring range of the inputs.

Make sure that the analog signal at the connection terminals is always within the signal range.

Range 0 … 10 V Digital value
    Decimal Hex.
Overflow > 11.7589 32767 7FFF
Measured value too high

11.7589

:

10.0004

32511

:

27649

7EFF

:

6C01

Normal range

10.0000

:

0.0004

27648

:

1

6C00

:

0001

0.0000 0 0000

The represented resolution corresponds to 10 bits.