Technical Data of the Module

Process supply voltages UP/UP3  
  Rated value 24 VDC (for inputs and outputs)
  Max. load for the terminals 10 A
  Protection against reversed voltage Yes
  Rated protection fuse on UP/UP3 10 A fast
  Electrical isolation ETHERNET interface against the rest of the module
  Inrush current from UP (at power up) On request
  Current consumption via UP (normal operation) 0.15 A
  Current consumption via UP3 0.06 A + 0.5 A max. per output
  Connections

Terminals 1.8 and 2.8 for +24 V (UP)

Terminal 3.8 for +24 V (UP3)

Terminals 1.9, 2.9 and 3.9 for 0 V (ZP)

Max. power dissipation within the module 6 W
Number of digital inputs 8
Number of digital outputs 8
Number of configurable digital inputs/outputs 8
Input data length 12 bytes
Output data length 20 bytes
Reference potential for all digital inputs and outputs Minus pole of the supply voltage, signal name ZP
Setting of the IO Device identifier With 2 rotary switches at the front side of the module
Diagnosis See Diagnosis and Displays CI502-PNIO (-XC)
Operation and error displays 34 LEDs (totally)
Weight (without Terminal Unit) Ca. 125 g
Mounting position Horizontal or vertical with derating (output load reduced to 50 % at 40 °C per group)
Extended ambient temperature (XC version) >60 °C on request
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Attention

:strong:Attention:

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.

No effects of multiple overloads

No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an internal smart high-side switch.

Bus connection 2 x RJ45
Switch Integrated
Technology Hilscher netX100
Transfer rate 10/100 MBit/s (full-duplex)
Transfer method According to ETHERNET II, IEE802.3
Expandability Max. 10 S500 I/O modules
Adjusting elements 2 rotary switches for generation of an explicit name
Supported protocols

RTC - real-time cyclic protocol, class 1 *

RTA - real-time acyclic protocol

DCP - discovery and configuration protocol

CL-RPC - connectionless remote procedure Call

LLDP - link layer discovery protocol

Acyclic services

PNIO read / write sequence (max. 1024 bytes per telegram)

Process-Alarm service

Supported alarm types Process Alarm, Diagnostic Alarm, Return of SubModule, Plug Alarm, Pull Alarm
Min. bus cycle 1 ms
Conformance Class CC A
Protective functions (according to IEC 61131-3)

Protected against:

- short circuit

- reverse supply

- overvoltage

- reverse polarity

Electrical isolation from the rest of the module

* Priorization with the aid of VLAN-ID including priority level