Technical Data

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Parameter Value
Protocol PROFINET I/O RT
Bus connection 2 x RJ45 (PNIO1 and PNIO2), with integrated 2-port switch
Switch Integrated
Technology Hilscher netX100
Transfer rate 100 MBit/s (full-duplex)
Transfer method According to ETHERNET II, IEE802.3
Bus length (segment length max.) 100 m
Indicators 5 LEDs
Usable terminal bases All TB5xx TB51x-TB54x
Supported alarm types Process alarm, diagnostic alarm, return of SubModule, plug alarm, pull alarm
Current consumption from 24 V DC power supply at the terminal base of the CPU Typ. 85 mA
Internal supply Via the communication module interface of the terminal base
Setting of the I/O device identifier With 2 rotary switches at the front side of the module
Weight Ca. 170 g
Supported protocols

RTC - real-time cyclic protocol, class 1

RTA - real-time acyclic protocol

DCP - discovery and configuration protocol *

CL-RPC - connectionless remote procedure call

LLDP - link layer discovery protocol

SNMP - simply network management protocol

MRP - MRP Client

Acyclic services

PNIO read / write

CM589-PNIO < FW 1.4.0: max. 1024 bytes

CM589-PNIO ≥ FW 1.4.0: max. 8096 bytes

CM589-PNIO-4: max. 8096 bytes

Total quantity of input and output data

CM589-PNIO < FW 1.4.0 (respectively for input and output): max. 1024 byte

CM589-PNIO ≥ FW 1.4.0 (respectively for input and output): max. 1440 byte

CM589-PNIO-4 (respectively for input and output): max. 1440 byte

Min. bus cycle 1 ms
Conformance class CC B

* Setting NameOfStation via service “DCP SET NameOfStation” is enabled only if rotary switches are adjusted to position “00”.