Characteristics of CI50x-PNIOΒΆ
Bus connection | 2 x RJ45 |
Switch | Integrated |
Technology | Hilscher netX100 |
Transfer rate | 10/100 MBit/s (full-duplex) |
Transfer method | According to ETHERNET II, IEE802.3 |
Expandability | Max. 10 S500 I/O modules |
Adjusting elements | 2 rotary switches for generation of an explicit name |
Supported protocols | RTC - real-time cyclic protocol, class 1 * RTA - real-time acyclic protocol DCP - discovery and configuration protocol CL-RPC - connectionless remote procedure Call LLDP - link layer discovery protocol |
Acyclic services | PNIO read / write sequence (max. 1024 bytes per telegram) Process-Alarm service |
Supported alarm types | Process Alarm, Diagnostic Alarm, Return of SubModule, Plug Alarm, Pull Alarm |
Min. bus cycle | 1 ms |
Conformance Class | CC A |
Protective functions (according to IEC 61131-3) | Protected against: - short circuit - reverse supply - overvoltage - reverse polarity Electrical isolation from the rest of the module |
* Priorization with the aid of VLAN-ID including priority level