Parameterization

Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is performed by Control Builder Plus/ Automation_Builder software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Module: Module slot address: Y = 1…10

Name Value Internal value Internal value, type Default Min. Max. EDS Slot/Index
Module ID Internal

1210

1)

Word

1210

0x04BA

0 65535 0x0Y01

Ignore module

2)

No

Yes

0

1

Byte

No

0x00

    Not for FBP
Parameter length Internal 5 Byte

5-CPU

4-FBP

0 255 0x0Y02
Check supply

Off

On

0

1

Byte

On

0x01

0 1 0x0Y03
Input delay

0.1 ms

1 ms

8 ms

32 ms

0

1

2

3

Byte

8 ms

0x02

0 3 0x0Y04

Fast Counter

4)

0

:

10

3)

0

:

10

Byte

Mode 0

0x00

    Not for FBP
Behaviour of outputs at communication errors

Off

Last value

Substitute value

0

1+(n*5)

2+(n*5),

n <= 2

Byte

Off

0x00

0 2 0x0Y05

Substitute value at outputs)

Bit 7 = Output 7

Bit 0 = Output 0

0…

255

0…

0xff

Byte

0

0x00

0 255 0x0Y06

Remarks:

1) With CS31 and addresses smaller than 70 and FBP, the value is increased by 1
2) Not with FBP
3) For a description of the counter operating modes, please refer to the Fast Counter section Fast Counter
4) With FBP and without the parameter Fast Counter

GSD file:

Ext_User_Prm_Data_Len =

Ext_User_Prm_Data_Const

  1. =

7

0x04, 0xbb, 0x04, \

0x01, 0x02, 0x00, 0x00;