Digital Inputs/Outputs if Used as OutputsΒΆ

Parameter Value
Number of channels per module Max. 16 transistor outputs
Reference potential for all outputs Terminals 1.9, 2.9, 3.9 and 4.9 (minus pole of the process supply voltage, signal name ZP)
Common power supply voltage For all outputs: terminals 1.8, 2.8, 3.8 and 4.8 (plus pole of the process supply voltage, signal name UP)
Output voltage for signal 1 UP (-0.8 V)
Output delay (0->1 or 1->0) On request
Output current:  
  Rated value, per channel 500 mA at UP = 24 V
  Maximum value (all channels together) 10 A
Leakage current with signal 0 < 0.5 mA
Rated protection fuse on UP 10 A fast
Demagnetization when inductive loads are switched off With varistors integrated in the module (see figure below)
Switching frequency:  
  With resistive loads On request
  With inductive loads Max. 0.5 Hz
  With lamp loads Max. 11 Hz with max. 5 W
Short-circuit-proof / overload-proof Yes
Overload message (I > 0.7 A) Yes, after approx. 100 ms
Output current limitation Yes, automatic reactivation after short circuit/overload
Resistance to feedback against 24 V signals Yes
Max. cable length:  
  Shielded 1000 m
  Unshielded 600 m

The following drawing shows the circuitry of a digital input/output with the varistors for demagnetization if inductive loads are switched off.

../_images/b7929b44e38830e60a33139000eba54e

Digital input/output (circuit diagram)