Diagnosis

In cases of short circuit or overload, the digital outputs are turned off. The modules performs reactivation automatically. Thus an acknowledgement of the errors is not necessary. The error message is stored via the LED.

E1..E4 d1 d2 d3 d4

Identifier

000..063

AC500-Display <− Display in
Class Comp Dev Mod Ch Err PS501 PLC Browser

Byte 6

Bit 6..7

- Byte 3 Byte 4 Byte 5

Byte 6

Bit 0..5

ETHCAT Diagnosis block
Class Interface Device Module Channel Error identifier Error message Remedy
  1) 2) 3) 4)      
Module error
3 - 31 31 31 19 Checksum error in the I/O module Replace I/O module
3 - 31 31 31 3 Timeout in the I/O module
3 - 31 31 31 40 Different hard-/firmware versions in the module
3 - 31 31 31 43 Internal error in the module
3 - 31 31 31 36 Internal data exchange failure
3 - 31 31 31 20 Slave-to-Slave malfunction Check configuration
3 - 31 31 31 41 Distributed Clock malfunction Check configuration
3 - 31 31 31 9 Overflow diagnosis buffer Restart
3 - 31 31 31 26 Parameter error Check master
3 - 31 31 31 11 Process voltage UP too low Check process supply voltage UP
4 - 31 31 31 45 Process voltage UP3 too low Check process voltage
4 - 31 31 31 34 No response during initialization of the I/O module Replace I/O module
4 - 31 31 31 46

Voltage feedback on activated digital outputs

4)

Check terminals
Channel error digital
4 - 31 2 0..7 46

Voltage feedback on deactivated digital output

5)

Check terminals
4 - 31 2 0..7 47 Short circuit at digital output Check terminals
Channel error analog
4 - 31 1 0..3 48 Analog value overflow or broken wire at an analog input Check value or check terminals
4 - 31 1 0..3 7 Analog value underflow at an analog input Check value
4 - 31 1 0..3 47 Short circuit at an analog input Check terminals
4 - 31 3 0..1 48 Analog value overflow at an analog output Check output value
4 - 31 3 0..1 7 Analog value underflow at an analog output Check output value

Remarks:

1)

In AC500 the following interface identifier applies:

“-” = Diagnosis via bus-specific function blocks; 0 … 4 or 10 = Position of the Communication Module;14 = I/O bus; 31 = Module itself

The identifier is not contained in the CI511-ETHCAT diagnosis block.

2)

With “Device” the following allocation applies:

31 = Module itself or ADR = Hardware address (e. g. of the DC551)

3)

With “Module” the following allocation applies dependent of the master:

31 = Module itself (Module error) or Module type (1=AI, 2=DO, 3=AO; channel error)

4) Diagnosis message appears for the whole output group and not per channel. The message occurs if the output channel is already active.
5) Diagnosis message appears per channel. The message occurs if the output channel is not active.