Connection of Analog Output Loads (Voltage, Current)¶
The following figure shows the connection of analog output loads (voltage, current).
Connection of analog output loads (voltage, current)
Voltage | -10 V…+10 V | Load ±10 mA max. | 1 channel used |
Current | 0…20 mA | Load 0…500 Ω | 1 channel used |
Current | 4…20 mA | Load 0…500 Ω | 1 channel used |
The measuring ranges are described in the section Measuring Ranges CI511-ETHCAT CI511-ETHCAT.
Unused analog outputs can be left open-circuited.