Connection of Analog Output Loads (Voltage, Current)

The following figure shows the connection of analog output loads (voltage, current).

../_images/03e88bd66b16ec100a33139033a06b13

Connection of analog output loads (voltage, current)

Voltage -10 V…+10 V Load  ±10 mA max. 1 channel used
Current 0…20 mA Load 0…500 Ω 1 channel used
Current 4…20 mA Load 0…500 Ω 1 channel used

The measuring ranges are described in the section Measuring Ranges CI511-ETHCAT CI511-ETHCAT.

Unused analog outputs can be left open-circuited.