Channel \ Parameters for the Analog Outputs (2x)

Name Value Internal value Internal value, type Default
Output 0, channel configuration see 3) see 3) BYTE 0
Output 0, check channel see 4) see 4) BYTE 0
Output 0, substitute value see 5) see 5) WORD 0
Output 1, channel configuration see 3) see 3) BYTE 0
Output 1, check channel see 4) see 4) BYTE 0
Output 1, substitute value see 5) see 5) WORD 0
Channel Configuration 3)
Internal value Operating modes of the analog outputs, individually configurable
0 Not used (default)
128 -10 V…+10 V
129 0…20 mA
130 4…20 mA
Channel Monitoring 4)
Internal value Check channel
0 Plausib(ility), cut wire, short circuit
3 None
Substitute Value 5)
Intended behaviour of output channel  when the control system stops Required setting of the module parameter “Behaviour of outputs in case of a communication error” Required setting of the channel parameter “Substitute value”
Output OFF Off 0
Last value infinite Last value 0
Last value for  5 s Last value 5 s 0
Last value for 10 s Last value 10 s 0
Substitute value infinite Substitute value Depending on configuration
Substitute value for 5 s Substitute value 5 s Depending on configuration
Substitute value for 10 s Substitute value 10 s Depending on configuration