Number of channels per module |
2 |
Distribution of channels into groups |
1 group for 2 channels |
Connection of the channels AO0+…AO1+ |
Terminals 1.5…1.6 |
Reference potential for AO0+ to AO1+ |
Terminal 1.7 (AO-) for voltage outputTerminal 1.9, 2.9 and 3.9 for current output |
Output type |
|
|
Unipolar |
Current |
|
Bipolar |
Voltage |
Electrical isolation |
Against internal supply and other modules |
Configurability |
-10…+10 V, 0…20 mA, 4…20 mA (each output can be configured individually) |
Output resistance (load), as current output |
0…500 W |
Output loadability, as voltage output |
± 10 mA max. |
Indication of the output signals |
1 LED per channel (brightness depends on the value of the analog signal) |
Resolution |
12 bits (+ sign) |
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range |
Typ. 0.5 %, max. 1 % |
Relationship between input signal and hex code |
Table Output ranges voltage and current CI501-PNIO |
Unused outputs |
Are configured as “unused” (default value) and can be left open-circuited |