| Number of channels per module |
16 outputs (with transistors) |
| Distribution of the channels into groups |
1 group of 16 channels |
| Connection of the channels |
|
| |
DO0 to DO7 |
Terminals 1.0 to 1.7 |
| |
DO8 to DO15 |
Terminals 2.0 to 2.7 |
| Indication of the output signals |
1 yellow LED per channel, the LED is ON if the output signal is high (signal 1) |
| Reference potential for all outputs |
Terminals 1.9, 2.9, 3.9 and 4.9 (negative pole of the process supply voltage, signal name ZP) |
| Common power supply voltage |
For all outputs: terminals 1.8, 2.8, 3.8 and 4.8 (positive pole of the process supply voltage, signal name UP) |
| Output voltage for signal 1 |
UP (-0.8 V) |
| Output delay (0->1 or 1->0) |
On request |
| Output current |
|
| |
Rated value, per channel |
500 mA at UP = 24 V |
| |
Maximum value (channels O0 to O15) |
4 A |
| Leakage current with signal 0 |
< 0.5 mA |
| Rated protection fuse on UP |
10 A fast |
| Demagnetization when inductive loads are switched off |
With varistors integrated in the module (see figure below) |
| Switching frequency |
|
| |
With resistive load |
On request |
| |
With inductive loads |
Max. 0.5 Hz |
| |
With lamp loads |
Max. 11 Hz with max. 5 W |
| Short-circuit-proof / overload-proof |
Yes |
| Overload message (I > 0.7 A) |
Yes, after ca. 100 ms |
| Output current limitation |
Yes, automatic reactivation after short circuit/overload |
| Resistance to feedback against 24V signals |
Yes |
| Max. cable length |
|
| |
Shielded |
1000 m |
| |
Unshielded |
600 m |