Technical data of the digital inputs/outputs if used as outputs

Parameter Value
Number of channels per module 8
Distribution of the channels into groups 1 group of 8 channels
Terminals of the channels DC16 to DC23 Terminals 4.0 to 4.7
Reference potential for all outputs Terminals 1.9…4.9 (negative pole of the supply voltage, signal name ZP)
Common power supply voltage For all outputs terminals 1.8, 2.8, 3.8 and 4.8 (positive pole of the supply voltage, signal name UP)
Output voltage for signal 1 UP (-0.8 V)
Output delay (0->1 or 1->0) On request
Output current  
  rated value per channel 500 mA at UP = 24 V
  max. value (all channels together) 4 A
Leakage current with signal 0 < 0.5 mA
Fuse for UP 10 A fast
Demagnetization with inductive DC load Via internal varistors (see figure below this table)
Output switching frequency  
  With resistive load On request
  With inductive loads Max. 0.5 Hz
  With lamp loads 11 Hz max. at 5 W max.
Short-circuit-proof / overload-proof Yes
Overload message (I > 0.7 A) Yes, after ca. 100 ms
Output current limitation Yes, automatic reactivation after short-circuit/overload
Resistance to feedback against 24V signals Yes (software-controlled supervision)
Max. cable length  
  Shielded 1000 m
  Unshielded 600 m

The following drawing shows the circuitry of a digital input/output with the varistors for demagnetization when inductive loads are switched off.

../_images/a2e8a9068eee14040a3313902cfe7c1c

Digital input/output (circuit diagram)