Connection of resistance thermometers in 2-wire configuration to the \ analog inputs

When resistance thermometers (Pt100, Pt1000, Ni1000) are used, a constant current must flow through them to build the necessary voltage drop for the evaluation. For this, the module CI541-DP provides a constant current source which is multiplexed over the max. 4 analog input channels.

The following figure shows the connection of resistance thermometers in 2-wire configuration to the analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.

../_images/ac6f42587129addc0a331390752e8f5f

The following measuring ranges can be configured CI541-DP CI541-DP:

Pt100 -50 °C…+400 °C 2-wire configuration, 1 channel used
Pt1000 -50 °C…+400 °C 2-wire configuration, 1 channel used
Ni1000 -50 °C…+150 °C 2-wire configuration, 1 channel used

The function of the LEDs is described under Diagnosis and displays / Displays CI541-DP.

The module CI541-DP performs a linearization of the resistance characteristic.

To avoid error messages from unused analog input channels, configure them as “unused”.