Connection of resistance thermometers in 2-wire configuration to the \ analog inputs¶
When resistance thermometers (Pt100, Pt1000, Ni1000) are used, a constant current must flow through them to build the necessary voltage drop for the evaluation. For this, the module CI541-DP provides a constant current source which is multiplexed over the max. 4 analog input channels.
The following figure shows the connection of resistance thermometers in 2-wire configuration to the analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.
The following measuring ranges can be configured CI541-DP CI541-DP:
Pt100 | -50 °C…+400 °C | 2-wire configuration, 1 channel used |
Pt1000 | -50 °C…+400 °C | 2-wire configuration, 1 channel used |
Ni1000 | -50 °C…+150 °C | 2-wire configuration, 1 channel used |
The function of the LEDs is described under Diagnosis and displays / Displays CI541-DP.
The module CI541-DP performs a linearization of the resistance characteristic.
To avoid error messages from unused analog input channels, configure them as “unused”.