Mounting on Terminal Units TU517 or TU518ΒΆ
The assignment of the terminals 1.0 - 1.9:
Terminal | Signal | Description |
---|---|---|
1.0 | B | Data line B (receive and send line, positive) |
1.1 | B | Data line B (receive and send line, positive) |
1.2 | A | Data line A (receive and send line, negative) |
1.3 | A | Data line A (receive and send line, negative) |
1.4 | TermB | Bus termination data line B |
1.5 | TermB | Bus termination data line B |
1.6 | TermA | Bus termination data line A |
1.7 | TermA | Bus termination data line A |
1.8 | DGND | Reference potential for data transmission |
1.9 | DGND | Reference potential for data transmission |
At the line ends of a bus segment, termination resistors must be connected. If using TU517/TU518, the bus termination resistors can be enabled by connecting the terminals TermA and TermB to the data lines A and B (no external termination resistors are required, see illustration below).
Note
If using TU517/TU518, note that the termination resistors are not located inside the TU, but inside the Bus Module CI541-DP. I. e. when removing the device from the TU, the bus termination resistors are not connected to the bus any more. The bus itself will not be disconnected if a device is removed.
If using TU517/TU518 the max. permitted baud rate is limited to 1,5 MBaud.
Note
The earthing of the shield should take place at the switch-gear cabinet, see System Data AC500 System Data AC500.