LED Status Display

The LEDs are located at the front of module. There are 2 different groups:

  • The 5 system LEDs (PWR, STA1-DP, STA2-DP, S-ERR and I/O-Bus) show the operation status of the module and display possible errors.
  • The 27 process LEDs (UP, UP3, inputs, outputs, CH-ERR1 to CH-ERR3) show the process supply voltage and the statuses of the inputs and outputs and display possible errors.
Status of the 5 System-LEDs:
LED Color OFF ON Flashing
PWR/RUN Green Process supply voltage missing Internal supply voltage OK, module ready for communication with IO Controller Start-up / preparing communication
Yellow
STA1-DP Green PROFIBUS running Invalid device parameters
STA2-DP Red No error Bus timeout No communication to Master
S-ERR Red No error Internal error
I/O-Bus Green No expansion modules connected or communication error Expansion modules connected and operational
Status of the 27 process LEDs:
LED Color OFF ON Flashing
AI0 to AI3 Yellow Input is OFF Input is ON (brightness depends on the value of the analog signal)
AO0 to AO1 Yellow Output is OFF Output is ON (brightness depends on the value of the analog signal)
DI0 to DI7 Yellow Input is OFF Input is ON (the input voltage is even displayed if the supply voltage is OFF)
DO0 toDO7 Yellow Output is OFF Output is ON
UP Green Process supply voltage missing Process supply voltage OK and initialization finished
UP3 Green Process supply voltage missing Process supply voltage OK
CH-ERR1 to CH-ERR3 Red No error or process supply voltage missing Internal error Error on one channel of the corresponding group