LED Status Display

The LEDs are located at the front of module. There are 2 different groups:

  • The 5 system LEDs (PWR, STA1-DP, STA2-DP, S-ERR and I/O-Bus) show the operation status of the module and display possible errors.
  • The 27 process LEDs (UP, UP3, inputs, outputs, CH-ERR1 to CH-ERR3) show the process supply voltage and the statuses of the inputs and outputs and display possible errors.
Status of the 5 System-LEDs:
LED Color OFF ON Flashing
PWR/RUN Green Process supply voltage missing Internal supply voltage OK, module ready for communication with IO Controller Start-up / preparing communication
Yellow — — —
STA1-DP Green — PROFIBUS running Invalid device parameters
STA2-DP Red No error Bus timeout No communication to Master
S-ERR Red No error Internal error –
I/O-Bus Green No expansion modules connected or communication error Expansion modules connected and operational —
Status of the 27 process LEDs:
LED Color OFF ON Flashing
AI0 to AI3 Yellow Input is OFF Input is ON (brightness depends on the value of the analog signal) –
AO0 to AO1 Yellow Output is OFF Output is ON (brightness depends on the value of the analog signal) –
DI0 to DI7 Yellow Input is OFF Input is ON (the input voltage is even displayed if the supply voltage is OFF) –
DO0 toDO7 Yellow Output is OFF Output is ON –
UP Green Process supply voltage missing Process supply voltage OK and initialization finished –
UP3 Green Process supply voltage missing Process supply voltage OK –
CH-ERR1 to CH-ERR3 Red No error or process supply voltage missing Internal error Error on one channel of the corresponding group