Channel \ parameters for the analog outputs (2x)¶
| Name | Value | Internal value | Internal value, type | Default |
|---|---|---|---|---|
| Output 0, Channel configuration | Operation modes of analog outputs CI541-DP | Operation modes of analog outputs CI541-DP | BYTE | 0 |
| Output 0, Check channel | Channel monitoring CI541-DP | Channel monitoring CI541-DP | BYTE | 0 |
| Output 0, Substitute value | Substitute value CI541-DP | Substitute value CI541-DP | WORD | 0 |
| Output 1, Channel configuration | Operation modes of analog outputs CI541-DP | Operation modes of analog outputs CI541-DP | BYTE | 0 |
| Output 1, Check channel | Channel monitoring CI541-DP | Channel monitoring CI541-DP | BYTE | 0 |
| Output 1, Substitute value | Substitute value CI541-DP | Substitute value CI541-DP | WORD | 0 |
Channel configuration
| Internal value | Operating modes of the analog outputs, individually configurable |
|---|---|
| 0 (default) | Not used |
| 128 | -10 V…+10 V |
| 129 | 0…20 mA |
| 130 | 4…20 mA |
Channel monitoring
| Internal value | Check channel |
|---|---|
| 0 | Plausib(ility), Cut wire, Short circuit |
| 3 | None |
Substitute value
| Intended behaviour of output channel when the control system stops | Required setting of the module parameter “Behaviour of outputs in case of a communication error” | Required setting of the channel parameter “Substitute value” |
|---|---|---|
| Output OFF | Off | 0 |
| Last value infinite | Last value | 0 |
| Last value for 5 s and then turn off | Last value 5 sec | 0 |
| Last value for 10 s and then turn off | Last value 10 sec | 0 |
| Substitute value infinite | Substitute value | depending on configuration |
| Substitute value for 5 s and then turn off | Substitute value 5 sec | depending on configuration |
| Substitute value for 10 s and then turn off | Substitute value 10 sec | depending on configuration |