Input Ranges Resistance

The resolution corresponds to 16 bits.

Range

Pt100 / Pt 1000

-50…70 °C

Pt100 / Pt1000

-50…400 °C

Ni1000

-50…150 °C

Digital value
        Decimal Hex.
Overflow > 80.0 °C > 450.0 °C > 160.0 °C 32767 7FFF
Measured value too high  

450.0 °C

:

400.1 °C

 

4500

:

4001

1194

:

0FA1

   

160.0 °C

:

150.1 °C

1600

:

1501

0640

:

05DD

80.0 °C

:

70.1 °C

   

800

:

701

0320

:

02BD

Normal

range

:

:

70.0 °C

:

0.1 °C

400.0 °C

:

:

:

0.1 °C

:

150.0 °C

:

:

0.1 °C

4000

1500

700

:

1

0FA0

05DC

02BC

:

0001

0.0 °C 0.0 °C 0.0 °C 0 0000

-0.1 °C

:

-50.0 °C

-0.1 °C

:

-50.0 °C

-0.1 °C

:

-50.0 °C

-1

:

-500

FFFF

:

FE0C

Measured value too low

-50.1 °C

:

-60.0 °C

-50.1 °C

:

-60.0 °C

-50.1 °C

:

-60.0 °C

-501

:

-600

FE0B

:

FDA8

Underflow < -60.0 °C < -60.0 °C < -60.0 °C -32768 8000