Input Ranges Resistance¶
The resolution corresponds to 16 bits.
| Range | Pt100 / Pt 1000 -50…70 °C  | 
Pt100 / Pt1000 -50…400 °C  | 
Ni1000 -50…150 °C  | 
Digital value | |
|---|---|---|---|---|---|
| Decimal | Hex. | ||||
| Overflow | > 80.0 °C | > 450.0 °C | > 160.0 °C | 32767 | 7FFF | 
| Measured value too high | 450.0 °C : 400.1 °C  | 
4500 : 4001  | 
1194 : 0FA1  | 
||
160.0 °C : 150.1 °C  | 
1600 : 1501  | 
0640 : 05DD  | 
|||
80.0 °C : 70.1 °C  | 
800 : 701  | 
0320 : 02BD  | 
|||
Normal range  | 
: : 70.0 °C : 0.1 °C  | 
400.0 °C : : : 0.1 °C  | 
: 150.0 °C : : 0.1 °C  | 
4000 1500 700 : 1  | 
0FA0 05DC 02BC : 0001  | 
| 0.0 °C | 0.0 °C | 0.0 °C | 0 | 0000 | |
-0.1 °C : -50.0 °C  | 
-0.1 °C : -50.0 °C  | 
-0.1 °C : -50.0 °C  | 
-1 : -500  | 
FFFF : FE0C  | 
|
| Measured value too low | -50.1 °C : -60.0 °C  | 
-50.1 °C : -60.0 °C  | 
-50.1 °C : -60.0 °C  | 
-501 : -600  | 
FE0B : FDA8  | 
| Underflow | < -60.0 °C | < -60.0 °C | < -60.0 °C | -32768 | 8000 |