Connection of resistance thermometers in 3-wire configuration

When resistance thermometers (Pt100, Pt1000, Ni1000) are used, a constant current must flow through them to build the necessary voltage drop for the evaluation. For this, the module AI523 provides a constant current source which is multiplexed over the max. 8 (depending on the configuration) analog channels.

../_images/948e5fb3e3880e3a0a331390015ea5a7

Connection example

Note

If several measuring points are adjacent to each other, the return line is necessary only once. This saves wiring costs.

With 3-wire configuration, two adjacent analog channels belong together (e.g. the channels 0 and 1). In this case, both channels are configured according to the desired operating mode. The lower address must be the even address (channel 0), the next higher address must be the odd address (channel 1).

The constant current of one channel flows through the resistance thermometer. The constant current of the other channel flows through one of the cores. The module calculates the measured value from the two voltage drops and stores it under the input with the higher channel number (e.g. I1).

In order to keep measuring errors as small as possible, it is necessary to have all the involved conductors in the same cable. All the conductors must have the same cross section.

The following measuring ranges can be configured AI523 - Analog Input Module

Pt100 -50 °C…+70 °C 3-wire configuration, two channels used
Pt100 -50 °C…+400 °C 3-wire configuration, two channels used
Pt1000 -50 °C…+400 °C 3-wire configuration, two channels used
Ni1000 -50 °C…+150 °C 3-wire configuration, two channels used

The function of the LEDs is described under Displays AI523 - Analog Input Module.

The module AI523 performs a linearization of the resistance characteristic.

In order to avoid error messages from unused analog input channels, it is useful to configure them as “unused”.