Technical \ Data of the Digital Inputs¶
Parameter | Value | |
---|---|---|
Number of channels per module | 16 | |
Distribution of the channels into groups | 1 group of 16 channels | |
Terminals of the channels I0 to I7 | 1.0 to 1.7 | |
Terminals of the channels I8 to I15 | 2.0 to 2.7 | |
Reference potential for all inputs | Terminals 1.9, 2.8, 3.8 and 4.9 (negative pole of the process supply voltage, signal name ZP) | |
Galvanic isolation | From the rest of the module (I/O bus) | |
Indication of the input signals | 1 yellow LED per channel, the LED is ON when the input signal is high (signal 1) | |
Input type acc. to EN 61131-2 | Type 1 | |
Input delay (0->1 or 1->0) | Typ. 8 ms, configurable from 0.1 to 32 ms | |
Input signal voltage | 24 VDC | |
Signal 0 | -3 V…+5 V | |
Undefined signal | > +5 V…< +15 V Parameter |
|
Signal 1 | +15 V…+30 V | |
Ripple with signal 0 | Within -3 V…+5 V | |
Ripple with signal 1 | Within +15 V…+30 V | |
Input current per channel | ||
Input voltage +24 V | Typ. 5 mA | |
Input voltage +5 V | > 1 mA | |
Input voltage +15 V | > 5 mA | |
Input voltage +30 V | < 8 mA | |
Max. cable length | ||
Shielded | 1000 m | |
Unshielded | 600 m |