Parameterization

Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is performed by Control Builder Plus/ Automation_Builder software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Module: Module slot address: Y = 1…10

No. Name Value Internal value Internal value, type Default Min. Max. EDS Slot/Index
1 Module ID Internal

1505

1)

Word

1505

0x05E1

0 65535 0x0Y01
2

Ignore module

2)

No

Yes

0

1

Byte

No

0x00

    Not for FBP
3 Parameter length in bytes Internal 21 Byte

21-CPU

21-FBP

0 255 0x0Y02
4 Check supply

Off

On

0

1

Byte

On

0x01

0 1 0x0Y03
5 Analog data format Default 0 Byte

Default

0x00

    0x0Y04
6 Behaviour of outputs at communication errors

Off

Last value

Substitute value

0

1+(n*5)

2+(n*5),

n <= 2

Byte

Off

0x00

0 2 0x0Y05
7

Channel configuration

Input channel 0

see table

“Channel configuration”

Byte

Default

0x00

0 19 0x0Y06
8

Channel monitoring

Input channel 0

see table

“Channel monitoring”

Byte

Default

0x00

0 3 0x0Y07

9

to

14

Channel configuration and channel monitoring of the input channels 1 to 3

see tables

“Channel configuration” and “Channel monitoring”

Byte

Byte

Default

0x00

0x00

0

0

19

3

0x0Y08

to

0x0Y0D

15

Channel configuration

Output channel 0

see table

“Channel configuration”

Byte

Default

0x00

0 130 0x0Y0E
16

Channel monitoring

Output channel 0

see table

“Channel monitoring”

Byte

Default

0x00

0 3 0x0Y0F
17

Substitute value

Output channel 0

only valid for output channel 0 0…0xffff Word

Default

0x0000

0 65535 0x0Y10
18 to 21 Channel configuration and channel monitoring of the output channels 1 to 2

see tables

“Channel configuration” and “Channel monitoring”

Byte

Byte

Default

0x00

0x00

0

0

130

3

0x0Y11

to

0x0Y14

22

Channel configuration

Output channel 3

see table

“Channel configuration”

Byte

Default

0x00

0 130 0x0Y15
23

Channel monitoring

Output channel 3

see table

“Channel monitoring”

Byte

Default

0x00

0 3 0x0Y16

1) With CS31 and addresses less than 70 and FBP, the value is increased by 1

2) Not with FBP

GSD file:

Ext_User_Prm_Data_Len =

Ext_User_Prm_Data_Const(0) =

24

0x05, 0xe2, 0x15, \

0x01, 0x00, 0x00 \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00;

Input channel (4x)
No. Name Internal value, type Default
1

Channel configuration

see table 2)

Byte

0

0x00 see table 2)

2

Channel monitoring

see table 3)

Byte

0

0x00 see table 3)

Channel configuration 2)
Internal value Operating modes of the analog inputs, individually configurable
0 Unused (default)
1 Analog input 0…10 V
2 Digital input
3 Analog input 0…20 mA
4 Analog input 4…20 mA
5 Analog input -10 V…+10 V
8 Analog input Pt100, -50 °C…+400 °C (2-wire)
9 Analog input Pt100, -50 °C…+400 °C (3-wire), requires 2 channels *)
10 Analog input 0…10 V via differential inputs, requires 2 channels *)
11 Analog input -10 V…+10 V via differential inputs, requires 2 channels *)
14 Analog input Pt100, -50 °C…+70 °C (2-wire)
15 Analog input Pt100, -50 °C…+70 °C (3-wire), requires 2 channels *)
16 Analog input Pt1000, -50 °C…+400 °C (2-wire)
17 Analog input Pt1000, -50 °C…+400 °C (3-wire), requires 2 channels *)
18 Analog input Ni1000, -50 °C…+150 °C (2-wire)
19 Analog input Ni1000, -50 °C…+150 °C (3-wire), requires 2 channels *)
  *) In the operating modes with 3-wire configuration or with differential inputs, two adjacent analog inputs belong together (e.g. the channels 0 and 1). In these cases, both channels are configured in the desired operating mode. The lower address must be the even address (channel 0). The next higher address must be the odd address (channel 1). The converted analog value is available at the higher address (channel 1).
Channel monitoring 3)
Internal value Monitoring
0 Plausibility, open-circuit (broken wire) and short-circuit
3 No monitoring
Output channel 0 (1 channel)
No. Name Value Internal value Internal value, type Default
1 Channel configuration see table 4) see table 4) Byte see table 4)
2 Channel monitoring see table 5) see table 5) Byte see table 5)
3

Substitute value

see table 6)

0…65535

0…

0xffff

Word 0
Output \ channels 1…3 (3x)
No. Name Internal value, type
1

Channel configuration

see table 4)

Byte
2

Channel monitoring

see table 6)

Byte
Channel configuration 4)
Internal value Operating modes of the analog outputs, individually configurable
0 Unused (default)
128 Analog output -10 V…+10 V
129 Analog output 0…20 mA (not with the channels 4…7 and 12…15)
130 Analog output 4…20 mA (not with the channels 4…7 and 12…15)
Channel monitoring 5)
Internal value Monitoring
0 Plausibility, open circuit (broken wire) and short circuit (default)
3 No monitoring
Substitute \ value 6)
Intended behaviour of output channel when the control system stops Required setting of the module parameter “Behaviour of outputs in case of a communication error” Required setting of the channel parameter “Substitute value”
Output OFF Off 0
Last value infinite Last value 0
Last value for 5 s and then turn off Last value 5 sec 0
Last value for 10 s and then turn off Last value 10 sec 0
Substitute value infinite Substitute value Depending on configuration
Substitute value for 5 s and then turn off Substitute value 5 sec Depending on configuration
Substitute value for 10 s and then turn off Substitute value 10 sec Depending on configuration