Diagnosis¶
E1..E4 | d1 | d2 | d3 | d4 | Identifier 000..063 |
AC500-Display | <− Display in | |
---|---|---|---|---|---|---|---|---|
Class | Comp | Dev | Mod | Ch | Err | PS501 PLC Browser | ||
Byte 6 Bit 6..7 |
- | Byte 3 | Byte 4 | Byte 5 | Byte 6 Bit 0..5 |
PNIO diagnosis block | ||
Class | Interface | Device | Module | Channel | Error Identifier | Error message | Remedy | |
1) | 2) | 3) | 4) | |||||
Module error | ||||||||
3 | 14 | 1..10 | 31 | 31 | 19 | Checksum error in the I/O module | Replace I/O module | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 43 | Internal error in the module | Replace I/O module | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 9 | Overflow diagnosis buffer | Restart | |
11 / 12 | ADR | 1..10 | ||||||
4 | 14 | 1..10 | 31 | 31 | 26 | Parameter error | Check master | |
11 / 12 | ADR | 1..10 | ||||||
3 | 14 | 1..10 | 31 | 31 | 11 | Process voltage too low | Check process voltage | |
11 / 12 | ADR | 1..10 |
Remarks:
1) | In AC500 the following interface identifier applies: 14 = I/O bus, 11 = COM1 (e.g. CS31-Bus), 12 = COM2. The PNIO diagnosis block does not contain this identifier. |
2) | With “Device” the following allocation applies: 31 = module itself, 1..10 = decentralized communication interface module 1..10, ADR = Hardware address (e. g. of the DC551-CS31) |
3) | With “Module” the following allocation applies depending on the master: Module error: I/O bus or PNIO: 31 = module itself; COM1/COM2: 1..10 = expansion 1..10 Channel error: I/O bus or PNIO = module type (2 = DO); COM1/COM2: 1..10 = expansion 1..10 |
4) | In case of module errors, with channel “31 = Module itself” is output. |