FunctionalityΒΆ

Interface Bus A RS485, CS31 protocol, electrically isolated from other electronic.
Interface Bus B RS485, CS31 protocol, electrically isolated from other electronic.
Address switches Two rotary switches for setting the CS31 Bus address (00d to 99d).
I/O Bus I/O Bus to connect S500-I/O modules (max. 7).
Digital inputs/outputs 16 configurable digital inputs/outputs in one group: 24 V DC, 0.5 A (max.), short-circuit and overload protected.
High-speed counter Integrated, with many configurable operating modes.
LED displays For system statuses, signal statuses, errors and power supply.
External power supply Via UP and ZP terminal (process voltage: 24 V DC).
Effect of incorrect input terminal connection Wrong or no signal detected, no damage up to 35V
Required Terminal Unit TU552-CS31 TU551-CS31 and TU552-CS31 for CS31 Communication Interface Modules