Technical \ Data of the Analog Inputs

Parameter Value
Number of channels per module 16
Distribution of channels into groups 2 groups of 8 channels each

Connections of the channels I0- to I7-

Connections of the channels I0+ to I7+

Terminals 1.0 to 1.7

Terminals 2.0 to 2.7

Connections of the channels I8- to I15-

Connections of the channels I8+ to I15+

Terminals 3.0 to 3.7 Terminals 4.0 to 4.7
Input type Bipolar (not with current or Pt100/Pt1000/Ni1000)
Input data length 32 bytes
Galvanic isolation Against internal supply and other modules
Configurability 0…10 V, -10…+10 V, 0/4…20 mA, Pt100/1000, Ni1000 (each input can be configured individually)
Channel input resistance Voltage: > 100 kW, current: ca. 330 W
Time constant of the input filter Voltage: 100 µs, current: 100 µs
Indication of the input signals 1 LED per channel
Conversion cycle 2 ms (for 16 inputs), with Pt/Ni… 1 s
Resolution Range 0…10 V: 12 bits
Range -10…+10 V: 12 bits + sign
Range 0…20 mA: 12 bits
Range 4…20 mA: 12 bits
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range Typ.

± 0.5 % of full scale

at 25°C

Max.

± 1 % of full scale (all ranges)

at 0…60 °C or EMC disturbance

Relationship between input signal and hex code See tables Input Ranges Voltage, Current and Digital Input AI523 - Analog Input Module and Input Ranges Resistance AI523 - Analog Input Module
Unused voltage inputs Are configured as “unused”
Unused current inputs Have a low resistance, can be left open-circuited
Overvoltage protection Yes