Parameters of the Module

Name Value Internal value Internal value, type Default
Module ID 1) Internal 0x1C84 WORD 0x1C84
Parameter length Internal 54 BYTE 54
Error LED / Failsafe function (table error LED / Failsafe function CI581-CN) On 0 BYTE 0
Off by E4 1
Off by E3 2
On + failsafe 16
Off by E4 + failsafe 17
Off by E3 + failsafe 18
Reserved 0 0 ARRAY of 24 BYTES  
Check supply (UP and UP3) On 0 BYTE  
Off 1 1
Fast counter 0 0 BYTE 0
: :  
10 2) 10  

1) With a faulty ID, the Modules reports a “parameter error” and does not perform cyclic process data transmission

2) For a description of the counter operating modes, please refer to the Fast Counter section.

Settings “Error LED / Failsafe function”
Setting Description
On Error LED (S-ERR) lights up at errors of all error classes, failsafe mode off
Off by E4 Error LED (S-ERR) lights up at errors of error classes E1, E2 and E3, failsafe mode off
Off by E3 Error LED (S-ERR) lights up at errors of error classes E1 and E2, failsafe mode off
On +Failsafe Error LED (S-ERR) lights up at errors of all error classes, failsafe mode on *)
Off by E4 + Failsafe Error LED (S-ERR) lights up at errors of error classes E1, E2 and E3, failsafe mode on *)
Off by E3 + Failsafe Error LED (S-ERR) lights up at errors of error classes E1 and E2, failsafe mode on *)
*) The parameters Behavior analog outputs at communication error and Behavior digital outputs at communication error are only evaluated if the failsafe function is enabled.