Technical Data of the Module

Parameter Value
Process supply voltages UP/UP3  
  Rated value 24 VDC (for inputs and outputs)
  Max. load for the terminals 10 A
  Protection against reversed voltage Yes
  Rated protection fuse on UP/UP3 10 A fast
  Electrical isolation ETHERNET interface against the rest of the module
  Inrush current from UP (at power up) On request
  Current consumption via UP (normal operation) 0.2 A
  Current consumption via UP3 0.06 A + 0.5 A max. per output
  Connections

Terminals 1.8 and 2.8 for +24 V (UP)

Terminal 3.8 for +24 V (UP3)

Terminals 1.9, 2.9 and 3.9 for 0 V (ZP)

Max. power dissipation within the module 6 W
Number of digital inputs 8
Number of digital outputs 8
Number of analog inputs 4
Number of analog outputs 2
Reference potential for all digital inputs and outputs Minus pole of the supply voltage, signal name ZP
ETHERNET 10/100 base-TX, internal switch, 2 x RJ45 socket
Setting of the IP address With ABB IP config tool and 2 rotary switches at the front side of the module
Diagnose See Diagnosis and Displays CI521-MODTCP
Operation and error displays 32 LEDs (totally)
Weight (without terminal unit) Ca. 125 g
Mounting position Horizontal or vertical with derating (output load reduced to 50 % at 40 °C per group)
Extended ambient temperature (XC version) > 60 °C on request
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Attention

:strong:Attention:

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.