Technical Data of the Analog Outputs¶
| Parameter | Value | ||
|---|---|---|---|
| Number of channels per module | 16, of which channnels O0…O3 and O8…O11 for voltage and current, and channels O4…7 and O12…15 only for voltage | ||
| Distribution of channels into groups | 2 groups of 8 channels each | ||
Channels O0-…O7- Channels O0+…O7+  | 
Terminals 1.0…1.7 Terminals 2.0…2.7  | 
||
Channels O8-…O15- Channels O8+…O15+  | 
Terminals 3.0…3.7 Terminals 4.0…4.7  | 
||
| Output type | Bipolar with voltage, unipolar with current | ||
| Galvanic isolation | Against internal supply and other modules | ||
| Configurability | -10…+10 V, 0…20 mA, 4…20 mA (each output can be configured individually), current outputs only channels 0…3 and 8…11 | ||
| Output resistance (load), as current output | 0…500 W | ||
| Output loadability, as voltage output | Max. ±10 mA | ||
| Output data length | 32 bytes | ||
| Indication of the output signals | One LED per channel | ||
| Resolution | 12 bits (+ sign) | ||
| Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range | Typ. | ± 0.5 % of full scale at 25°C  | 
|
| Max. | ± 1 % of full scale (all ranges) at 0…60 °C or EMC disturbance  | 
||
| Relationship between output signal and hex code | Table output ranges voltage and current AO523 - Analog Output Module | ||
| Unused outputs | Can be left open-circuited | ||