Mechanical Data

Mounting Horizontal
Degree of protection IP 20 (if all terminal screws are tightened)
Housing According to UL 94
Vibration resistance acc. to EN 61131-2

all three axes (DIN rail mounting)

5 Hz … 11.9 Hz, continuous 3.5 mm

11.9 Hz … 150 Hz, continuous 1 g

Vibration resistance with SD Memory Card inserted 15 Hz…150 Hz, continuous 1 g
Shock test

All three axes

15 g, 11 ms, half-sinusoidal

Mounting of the modules:
DIN rail according to DIN EN 50022 35 mm, depth 7.5 mm or 15 mm
Mounting with screws Screws with a diameter of 4 mm
Fastening torque 1.2 Nm