Electrical Connection

The ETHERNET Bus Module CI506-PNIO is plugged on the Terminal Unit TU520-ETH TU520-ETH for PROFINET Communication Interface Modules. Properly seat the module and press until it locks in place. The Terminal Unit is mounted on a DIN rail or with 2 screws plus the additional accessory for wall mounting (TA526 TA526 - Wall Mounting Accessory).

The electrical connection of the power supply voltage is carried out using the 6 terminals and the 3 removable connectors of the Terminal Unit. The CI506-PNIO can be replaced without re-wiring the Terminal Units.

Note

For a detailed description of the mounting, disassembly and electrical connection of the module, please refer to the System Assembly, Construction and Connection chapter AC500 (Standard).

The terminals 1.0, 2.0 and 3.0 as well as 1.1, 2.1 and 3.1 are electrically interconnected within the Terminal Unit and have always the same assignment, independent of the inserted module:

Assignment of the terminals
Terminal Signal Description
1.0 UP Process voltage UP (+24 VDC)
1.1 ZP Process voltage ZP (0 VDC)
2.0 UP Process voltage UP (+24 VDC)
2.1 ZP Process voltage ZP (0 VDC)
3.0 UP Process voltage UP (+24 VDC)
3.1 ZP Process voltage ZP (0 VDC)
Assignment of the terminals of removable connectors X11 and \ X12 (Serial Interfaces)
Terminal Signal Description
1 Term-P RS-485 Internal line terminating resistor for non-inverted signal (Rx/Tx-P)
RS-422 Non-inverted receive signal terminal (RxD+)
2 Rx/Tx-P RS-485 Non-inverted I/O signal terminal for each channel
RS-422 Non-inverted transmit signal terminal (TxD+)
3 Rx/Tx-N RS-485 Inverted I/O signal terminal for each channel
RS-422 Inverted transmit signal terminal (TxD-)
4 Term-N RS-485 Internal line-terminating-resistor for inverted signal (Rx/Tx-N) terminal
RS-422 Inverted receive signal terminal (RxD-)
5 RTS RS-232 Request To Send signal terminal for each channel
6 TxD RS-232 Transmit signal terminal for each channel
7 SGND RS-232 Signal ground for each channel
8 RxD RS-232 Receive signal terminal for each channel
9 CTS RS-232 Clear To Send signal terminal for each channel

Note

The connection of SGND (ground) is optional for RS-485/RS-422.

Note

For RS-422, no external line-terminating resistors have to connected. They are already connected inside the module.

Assignment of the terminals of removable connector X13 (CANOPEN Interface)
Terminal Signal Description
1 TERM+ Internal line-terminating-resistor for CAN Bus. Bridging to CAN HIGH terminal if bus termination is required
2 CAN+ Non-inverted CAN data terminal
3 CAN- Inverted CAN data terminal
4 TERM- Internal line-terminating-resistor for CAN Bus. Bridging to CAN LOW terminal if bus termination is required
5 Not used Not used
6 Not used Not used
7 CAN_GND CAN ground terminal
8 Not used Not used
9 Not used Not used

Warning

:strong:Removal/Insertion under power

The devices are not designed for removal or insertion under power. Because of unforeseeable consequences, it is not allowed to plug or unplug devices with the power being ON.

Make sure that all voltage sources (supply and process voltage) are switched off before you

  • connect or disconnect any signal or terminal block
  • remove, mount or replace a module.

Disconnecting any powered devices while energized in a hazardous location could result in an electric arc, which could create a flammable ignition resulting in fire or explosion.

Make sure that power is removed and that the area has been thoroughly checked to ensure that flammable materials are not present prior to proceeding.

The devices must not be opened when in operation. The same applies to the network interfaces.

Attention

:strong:Risk of damaging the PLC modules!

Overvoltages and short circuits might damage the PLC modules.

  • Make sure that all voltage sources (supply and process voltage) are switched off before you begin with operations at the system.
  • Never connect any voltages or signals to reserved terminals (marked with —). Reserved terminals may carry internal voltages.

The module provide several diagnosis functions CI506-PNIO.

Further information is provided in the System Technology chapter PROFINET: PROFINET Communication Modules