Connection of analog output loads (voltage, current)

../_images/32bb9aec5ca6347f0a33139074e10109

Connection example

The following measuring ranges can be configured AO523 - Analog Output Module AO523 - Analog Output Module:

Voltage -10 V…+10 V Load max. ±10 mA 1 channel used
Current 0…20 mA Load 0…500 W 1 channel used
Current 4…20 mA Load 0…500 W 1 channel used

Only the channels 0…3 and 8…11 can be configured as current output (0…20 mA or 4…20 mA).

The function of the LEDs is described under Displays.

Unused analog outputs can be left open-circuited.