Parameterization

Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is performed by Control Builder Plus/ Automation_Builder software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Module: Module slot address: Y = 1…10

No. Name Value Internal value Internal value, type Default Min. Max. EDS Slot/Index
1 Module ID Internal

1510

1)

Word

1510

0x05e6

0 65535 0x0Y01
2

Ignore module

2)

No

Yes

0

1

Byte

No

0x00

    Not for FBP
3 Parameter length in bytes Internal 39 Byte

39-CPU

39-FBP

0 255 0x0Y02
4 Check supply

Off

On

0

1

Byte

On

0x01

0 1 0x0Y03
5 Analog data format Default 0 Byte

Default

0x00

    0x0Y04
6 Behaviour of outputs at communication errors

Off

Last value

Substitute value

0

1+(n*5)

2+(n*5),

n <= 2

Byte

Off

0x00

0 2 0x0Y05
7

Channel configura tion

Output channel 0

see table

“Channel configuration”

Byte

Default

0x00

0 130 0x0Y06
8

Channel monitori ng

Output channel 0

see table

“Channel monitoring”

Byte

Default

0x00

0 3 0x0Y07
9

Substitute value

Output channel 0

Output channel 0! 0…0xffff Word

Default

0x0000

0 65535 0x0Y08
10 to 15 Channel configuration and channel monitoring of the output channels 1 to 3

see tables

“Channel configuration” and “Channel monitoring”

Byte

Byte

Default

0x00

0x00

0

0

130

3

0x0Y09

to

0x0Y0E

16 to 23 Channel configuration and channel monitoring of the output channels 4 to 7

see tables

“Channel configuration” and “Channel monitoring”

Byte

Byte

Default

0x00

0x00

0

0

128

3

0x0Y0F

to

0x0Y16

24

Channel configura tion

Output channel 8

see table

“Channel configuration”

Byte

Default

0x00

0 130 0x0Y17
25

Channel monitorin g

Output channel 8

see table

“Channel monitoring”

Byte

Default

0x00

0 3 0x0Y18
26

Substitute value

Output channel 8

Output channel 8! 0…0xffff Word

Default

0x0000

0 65535 0x0Y19

27

to

32

Channel configuration and channel monitoring of the output channels 9 to 11

see tables

“Channel configuration” and “Channel monitoring”

Byte

Byte

Default

0x00

0x00

0

0

130

3

0x0Y1A

to

0x0Y1F

33

to

40

Channel configuration and channel monitoring of the output channels 12 to 15

see tables

“Channel configuration” and “Channel monitoring”

Byte

Byte

Default

0x00

0x00

0

0

128

3

0x0Y20

to

0x0Y27

1) With CS31 and addresses less than 70 and FBP, the value is increased by 1

2) Not with FBP

GSD file:

Ext_User_Prm_Data_Len =

Ext_User_Prm_Data_Const(0) =

42

0x05, 0xe7, 0x27, \

0x01, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00;

Output channels 0 and 8 (2 channels, AO523)

No. Name Value Internal value Internal value, type Default
1 Channel configuration see below AO523 - Analog Output Module see below AO523 - Analog Output Module Byte see below AO523 - Analog Output Module
2 Channel monitoring see below AO523 - Analog Output Module see below AO523 - Analog Output Module*8) Byte see below AO523 - Analog Output Module
3 Substitute value AO523 - Analog Output Module 0…65535

0…

0xffff

Word 0

Output \ channels 1…7 and 9…15 (14 channels, AO523)

No. Name Internal value, type
1

Channel configuration

see table 3)

Byte
2

Channel monitoring

see table 4)

Byte
Channel configuration 3)
Internal value Operating modes of the analog outputs, individually configurable
0 Unused (default)
128 Analog output -10 V…+10 V
129 Analog output 0…20 mA (not with the channels 4…7 and 12…15)
130 Analog output 4…20 mA (not with the channels 4…7 and 12…15)
Channel monitoring 4)
Internal value Monitoring
0 Plausibility, open-circuit (broken wire) and short-circuit (default)
1 Open-circuit (broken wire) and short-circuit
2 Plausibility
3 No monitoring
Substitute \ value
Intended behaviour of channel 0 when the control system stops Required setting of the module parameter “Behaviour of outputs in case of a communication error” Required setting of the channel parameter “Substitute value”
Output OFF OFF 0
Last value Last value 0
Substitute value OFF or Last value 1…65535