Parameterization¶
Firmware version | Configuration |
---|---|
Firmware version > V2.0.0 | The arrangement of the parameter data is performed by Control Builder Plus/ Automation_Builder software. |
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configuration.
Module: Module slot address: Y = 1…10
No. | Name | Value | Internal value | Internal value, type | Default | Min. | Max. | EDS Slot/Index |
---|---|---|---|---|---|---|---|---|
1 | Module ID | Internal | 1510 1) |
Word | 1510 0x05e6 |
0 | 65535 | 0x0Y01 |
2 | Ignore module 2) |
No Yes |
0 1 |
Byte | No 0x00 |
Not for FBP | ||
3 | Parameter length in bytes | Internal | 39 | Byte | 39-CPU 39-FBP |
0 | 255 | 0x0Y02 |
4 | Check supply | Off On |
0 1 |
Byte | On 0x01 |
0 | 1 | 0x0Y03 |
5 | Analog data format | Default | 0 | Byte | Default 0x00 |
0x0Y04 | ||
6 | Behaviour of outputs at communication errors | Off Last value Substitute value |
0 1+(n*5) 2+(n*5), n <= 2 |
Byte | Off 0x00 |
0 | 2 | 0x0Y05 |
7 | Channel configura tion Output channel 0 |
see table “Channel configuration” |
Byte | Default 0x00 |
0 | 130 | 0x0Y06 | |
8 | Channel monitori ng Output channel 0 |
see table “Channel monitoring” |
Byte | Default 0x00 |
0 | 3 | 0x0Y07 | |
9 | Substitute value Output channel 0 |
Output channel 0! | 0…0xffff | Word | Default 0x0000 |
0 | 65535 | 0x0Y08 |
10 to 15 | Channel configuration and channel monitoring of the output channels 1 to 3 | see tables “Channel configuration” and “Channel monitoring” |
Byte Byte |
Default 0x00 0x00 |
0 0 |
130 3 |
0x0Y09 to 0x0Y0E |
|
16 to 23 | Channel configuration and channel monitoring of the output channels 4 to 7 | see tables “Channel configuration” and “Channel monitoring” |
Byte Byte |
Default 0x00 0x00 |
0 0 |
128 3 |
0x0Y0F to 0x0Y16 |
|
24 | Channel configura tion Output channel 8 |
see table “Channel configuration” |
Byte | Default 0x00 |
0 | 130 | 0x0Y17 | |
25 | Channel monitorin g Output channel 8 |
see table “Channel monitoring” |
Byte | Default 0x00 |
0 | 3 | 0x0Y18 | |
26 | Substitute value Output channel 8 |
Output channel 8! | 0…0xffff | Word | Default 0x0000 |
0 | 65535 | 0x0Y19 |
27 to 32 |
Channel configuration and channel monitoring of the output channels 9 to 11 | see tables “Channel configuration” and “Channel monitoring” |
Byte Byte |
Default 0x00 0x00 |
0 0 |
130 3 |
0x0Y1A to 0x0Y1F |
|
33 to 40 |
Channel configuration and channel monitoring of the output channels 12 to 15 | see tables “Channel configuration” and “Channel monitoring” |
Byte Byte |
Default 0x00 0x00 |
0 0 |
128 3 |
0x0Y20 to 0x0Y27 |
|
1) With CS31 and addresses less than 70 and FBP, the value is increased by 1 2) Not with FBP |
GSD file:
Ext_User_Prm_Data_Len = Ext_User_Prm_Data_Const(0) = |
42 0x05, 0xe7, 0x27, \ 0x01, 0x00, 0x00, \ 0x00, 0x00, 0x00, 0x00, \ 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \ 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \ 0x00, 0x00, 0x00, 0x00, \ 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \ 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00; |
Output channels 0 and 8 (2 channels, AO523)
No. | Name | Value | Internal value | Internal value, type | Default |
---|---|---|---|---|---|
1 | Channel configuration | see below AO523 - Analog Output Module | see below AO523 - Analog Output Module | Byte | see below AO523 - Analog Output Module |
2 | Channel monitoring | see below AO523 - Analog Output Module | see below AO523 - Analog Output Module*8) | Byte | see below AO523 - Analog Output Module |
3 | Substitute value AO523 - Analog Output Module | 0…65535 | 0… 0xffff |
Word | 0 |
Output \ channels 1…7 and 9…15 (14 channels, AO523)
No. | Name | Internal value, type |
---|---|---|
1 | Channel configuration see table 3) |
Byte |
2 | Channel monitoring see table 4) |
Byte |
Internal value | Operating modes of the analog outputs, individually configurable |
---|---|
0 | Unused (default) |
128 | Analog output -10 V…+10 V |
129 | Analog output 0…20 mA (not with the channels 4…7 and 12…15) |
130 | Analog output 4…20 mA (not with the channels 4…7 and 12…15) |
Internal value | Monitoring |
---|---|
0 | Plausibility, open-circuit (broken wire) and short-circuit (default) |
1 | Open-circuit (broken wire) and short-circuit |
2 | Plausibility |
3 | No monitoring |
Intended behaviour of channel 0 when the control system stops | Required setting of the module parameter “Behaviour of outputs in case of a communication error” | Required setting of the channel parameter “Substitute value” |
---|---|---|
Output OFF | OFF | 0 |
Last value | Last value | 0 |
Substitute value | OFF or Last value | 1…65535 |