Input channel (2x)

Name Value Internal value Internal value, Type Default Min. Max.
Channel configuration see table 2) see table 2) BYTE

0

0x00 see table 3)

0 65535
Channel configuration 2)
Internal value Operating modes for the analog inputs, individually configurable
0

Not used (default)

3)

8 2-wire Pt100 -50 … +400 °C
9 3-wire Pt100 -50 … +400 °C
16 2-wire Pt1000, -50 … +400 °C
17 3-wire Pt1000, -50 … +400 °C
18 2-wire Ni1000 -50 … +150 °C
19 3-wire Ni1000 -50 … +150 °C
22 2-wire Ni100, -50 … +150 °C
23 3-wire Ni100, -50 … +150 °C
32 Analog input resistor 0 … 150 W
33 Analog input resistor 0 … 300 W