AC500 V3 Firmware UpdateΒΆ
Execute following steps to update the firmware for CPU by Automation_Builder 2.0:
Note
These steps are also necessary for commissioning V3 CPU.
Create a project with PLC_AC500_V3.
Right-click on CPU PLC_AC500_V3 (PM5650-2ETH).
Click Reset origin device [PLC_AC500_V3].
Reboot CPU β Power off/on
- β
CPU remains in Init now β UpdateFW active.
Open Tab of CPU and go to DeviceMaintenance.
Enter the IP address and click Execute update.
Note
:strong:Attention!
When status is showing, Update finished! After reboot the firmware is ready for operation, the CPU is still performing the update.
Check flashing LED!
LED | LED flashes | Status |
---|---|---|
RUN and ERR | Toggling | Update pending |
RUN | Flashing slow | Done successful |
ERR | Flashing slow | Done failed |