Parameters of PM5x1-ARCNET (onboard ARCNET)¶
Add a Processor Module with onboard ARCNET (e.g. PM590-ARC) to the device tree. Double-click the node PM5x1_ARC_Internal_ARCNET to open the parameter settings for onboard ARCNET. Check whether the default configuration is to be changed.
The following parameters are available:
Parameter | Default value | Value | Meaning |
---|---|---|---|
Run config fault | No | No | In case of a configuration error, the user program is not started. |
Yes | The user program is started independent of a faulty configuration of the internal ARCNET Communication Module. | ||
Address see remark 1 Parameters of PM5x1-ARCNET (onboard ARCNET) |
0 | 0…255 | Address (node ID) of the ARCNET Communication Module |
Baudrate see remark 2 Parameters of PM5x1-ARCNET (onboard ARCNET) |
2.5 MB/s | 2.5 MB/s | Baudrate set for the ARCNET Communication Module |
1.25 MB/s | |||
625 kB/s | |||
312.5 kB/s | |||
Extended timeout ET1/ET2 | Very small net | Very small net (=0) | ARCNET timeout setting. The following applies: Bit 0 configures ET2 of the Communication Module Bit 1 configures ET1 of the Communication Module Value ET1 ET2 Meaning ———————– 0 0 0 Max. network expansion 2 km 1 1 0 2 0 1 3 1 1 for large networks |
Small net (=1) | |||
Big net (=2) | |||
Very big net (=3) | |||
Long packets | Enable | Enable | Enable long data packages (512 bytes) |
Disable | Incoming long data packages are received and dismissed. The SEND block indicates an error in case of long data packages. | ||
Evaluate DIN on receipt see remark 3 Parameters of PM5x1-ARCNET (onboard ARCNET) |
Enable | Enable | Enable check of DIN identifier on receipt |
Disable | Disable check of DIN identifier on receipt |