Configuration of the IP Settings

In the Automation_Builder project, double-click the ETHERNET node to open the IP settings:

../_images/a15fcd2745ff82b90a33139000eba54e
Parameters:
Parameter Default Value Description

Parameter 1)

Configuration of the IP Settings)

Force IP settings Disabled Disabled The IP settings from this editor are not used. Use IP data
Enabled The IP settings from this editor are used. After download of the user application and subsequent logoff, the new IP settings are used temporarily until power off the device. For a permanent usage of the IP settings, create a boot project.
DHCP Disabled Disabled The DHCP client services are disabled. A static IP address must be used. IP mode (+ DHCP)
Enabled The DHCP client services are enabled. The IP address of the device will be set by a DHCP server in the network.
IP address 0.0.0.0 Valid IP address IP address of the device. IP address
Subnetmask 255.255.255.0 Valid subnet mask Subnet mask for the device. Netmask
Default gateway 0.0.0.0 Valid gateway address Default gateway address for the device. Gateway
Link mode Auto negotiation Auto negotiation The link mode will be detected automatically. Link mode
10 Mbit Half-Duplex The link mode is statically set to 10 Mbit half-duplex.
10 Mbit Full-Duplex The link mode is statically set to 10 Mbit full-duplex.
100 Mbit Half-Duplex The link mode is statically set to 100 Mbit half-duplex.
100 Mbit Full-Duplex The link mode is statically set to 100 Mbit full-duplex.
ABBNetConfig protocol active Enabled Enabled Remote configuration: ABB NetConfig protocol is enabled.  
Disabled Remote configuration: ABB NetConfig protocol is disabled.

Remarks:

1): Generic Device Configuration View Parameters

For a list of all available parameters, open the IP Settings Parameters. This tab is only visible after enabling parameter ‘Show generic device configuration views’ under Tools ‣ Options:

../_images/fac3629645ff83170a33139000eba54e