Configuration of the IP Settings¶
In the Automation_Builder project, double-click the ETHERNET node to open the IP settings:
Parameter | Default | Value | Description | Parameter 1) |
---|---|---|---|---|
Force IP settings | Disabled | Disabled | The IP settings from this editor are not used. | Use IP data |
Enabled | The IP settings from this editor are used. After download of the user application and subsequent logoff, the new IP settings are used temporarily until power off the device. For a permanent usage of the IP settings, create a boot project. | |||
DHCP | Disabled | Disabled | The DHCP client services are disabled. A static IP address must be used. | IP mode (+ DHCP) |
Enabled | The DHCP client services are enabled. The IP address of the device will be set by a DHCP server in the network. | |||
IP address | 0.0.0.0 | Valid IP address | IP address of the device. | IP address |
Subnetmask | 255.255.255.0 | Valid subnet mask | Subnet mask for the device. | Netmask |
Default gateway | 0.0.0.0 | Valid gateway address | Default gateway address for the device. | Gateway |
Link mode | Auto negotiation | Auto negotiation | The link mode will be detected automatically. | Link mode |
10 Mbit Half-Duplex | The link mode is statically set to 10 Mbit half-duplex. | |||
10 Mbit Full-Duplex | The link mode is statically set to 10 Mbit full-duplex. | |||
100 Mbit Half-Duplex | The link mode is statically set to 100 Mbit half-duplex. | |||
100 Mbit Full-Duplex | The link mode is statically set to 100 Mbit full-duplex. | |||
ABBNetConfig protocol active | Enabled | Enabled | Remote configuration: ABB NetConfig protocol is enabled. | |
Disabled | Remote configuration: ABB NetConfig protocol is disabled. |
Remarks:
1): Generic Device Configuration View Parameters
For a list of all available parameters, open the IP Settings Parameters. This tab is only visible after enabling parameter ‘Show generic device configuration views’ under :