Parameterization

The Encoder and PWM Module CD522 does not store configuration data itself. The digital inputs and outputs are used to specific counting functions depending to configuration mode chosen. All unused inputs and outputs can be used with the specification of standard input/output range.

For non-standard applications, it is necessary to adapt the parameters to your system configuration:

Name Type Value Default Internal Value Min. Max. EDS Slot Index
Ignore module *) BYTE

No

Yes

No

0x00

0

1

    Not for FBP
Check supply BYTE

Off

On

On

0x01

0

1

    0x0Y03
Input delay BYTE

0.1 ms

1 ms

8 ms

32 ms

8 ms

0x02

0

1

2

3

0 3 0x0Y04
Mode counter 0 BYTE see table below 0x00 0 0 15 0x0Y05
Freq limit FC0 BYTE

No filter

50 Hz

500 Hz

5 kHz

20 kHz

No filter

0x00

0

1

2

3

4

0 4 0x0Y06
Input level FC0 BYTE

0-24 V DC

0-5 V DC

Differential

1 Vpp sinus

0-24 V DC 0x00

0

1

2

3

0 3 0X0Y07
SSI 0 frequency BYTE

200 kHz

500 kHz

1 MHz

200 kHz

0x02

2

3

4

0 4 0x0Y08
SSI 0 resolution (in Bit) BYTE 8 to 32 bit

16 bit

16

  8 32 0x0Y09
SSI 0 code type BYTE Binary

Binary

0

0 0 0 0x0Y0A
SSI 0 polling time BYTE 10 ms 10   1 255 0x0Y0B
5 V sensor 0 supply BYTE

Off

On

Off

0x00

0 0 1 0x0Y0C
Mode counter 1 BYTE see table below 0x00 0 0 15 0x0Y0D
Freq limit FC1 BYTE

No filter

50 Hz

500 Hz

5 kHz

20 kHz

No filter

0x00

0

1

2

3

4

0 4 0x0Y0E
Input level FC1 BYTE

0-24 V DC

0-5 V DC

Differential

1 Vpp sinus

0-24 V DC 0x00

0

1

2

3

0 3 0X0Y0F
SSI 1 frequency BYTE

200 kHz

500 kHz

1 MHz

200 kHz

0x02

2

3

4

2 4 0x0Y10
SSI 1 resolution (in Bit) BYTE 8 to 32 bit

16 bit

16

  8 32 0x0Y11
SSI 1 code type BYTE Binary

Binary

0

0 0 0 0x0Y12
SSI 1 polling time BYTE 10 ms 10   1 255 0x0Y13
5 V sensor 1 supply BYTE

Off

On

Off

0x00

0 0 1 0x0Y14
Detection SC and sensors BYTE

Off

On

Off

0x00

0 0 1 0x0Y15
Behaviour outputs at comm. error BYTE

Off

Last value

Substitute

Last value 5s

Substitute 5s

Last value 10s Substitute 10s

Off

0x00

0

1

2

3

4

5

6

0 1 0x0Y16
Substitute value WORD 0

Default

0x0000

0 0 65536 0x0Y17

*) Not with FBP

Operating modes for counters 0 and 1:
Internal value Operating modes of counter
0 No counter / No PWM (default value)
1 1-1 UpDown counter (A)
2 2-1 UpDown with release input
3 3-2 UpDown counters (A, B)
4 4-2 UpDown (A, B on falling edges)
5 5-1 UpDown dynamic set (B) / rising edge
6 6-1 UpDown dynamic set (B) / falling edge
7 Not used
8 8-1 UpDown with release (B), 0 cross detection
9 - 19 Not used
20 11-1 Incremental encoder
21 12-2 Incremental encoder X2
22 13-1 Incremental encoder X4
30 14-1 SSI, absolute encoder
40 15-1 Time frequency meter