Transmission rate - Comparison with OPC Server V2 to V3ΒΆ

Some figures about OPC Server transmission rates of a special test setup of HHZ:

  • PC Lenovo T430, Windows 7, 64 bit
    • OPC client (OPC Systemtest Teststand, LabView 8.6 application)
    • OPC Server V2 und V3
  • AC500 PM592 (task freewheeling and t=2 ms shown similar values)
  • OPC client application: 100 cycles (write item, read item, compare value, increment value)
OPC Server Item Byte
  Connect [ms] Mean value [ms] Max. value [ms] Disconnect [ms]
OPC Server V2: write cycle 2 2.374 4 0
OPC Server V2: read cycle 2 127.2 133 0
OPC Server V3: write cycle 2 1.838 4 1
OPC Server V3: read cycle 2 96.8889 99 1
OPC Server Item Byte
  Connect [ms] Mean value [ms] Max. value [ms] Disconnect [ms]
OPC Server V2: write cycle 1 2.333 4 0
OPC Server V2: read cycle 1 127.152 133 0
OPC Server V3: write cycle 1 1.616 4 1
OPC Server V3: read cycle 1 97.1414 99 1