Behavior of the OPC Server V3 with DigiVis500ΒΆ
Setup
- Windows 7, Professional 32 bit, SP1
- DigiVis500_SP1
With DigiVis500 installation the ABB OPC Tunnel is installed and registered automatically as service (session 0) with Startup type: Automatic. Automatic means ABB OPC Tunnel will start as soon as the Windows system starts up.
With the start of the ABB OPC Tunnel (OCTsvc.exe), the OPCServer (WinCoDeSysOPC.exe) and also the IEC 61131-3 editor gateway server (Gateway.exe) are started in session 0.
Note
Communication of CBP or IEC 61131-3 editor (session 1) with AC500 is not possible more. They need the Gateway.exe in session 1, but the IEC 61131-3 editor gateway server is not able to run in multi sessions.
To use CBP or IEC 61131-3 editor, the OPC tunnel service must be stopped. This can be done in Component Service, Service (local), ABB OPC Tunnel with the Start, Stop buttons.
Windows Task Manager
BUBMAIN.EXE is DigiVis 500 Operation
Note
An example of a working setup on one PC with CBP into a virtual machine is described in Examples, OPC Client as a Windows service with CBP on the same PC.