Technical DataΒΆ

The MODBUS operating mode and the interface parameters are set in the PLC configuration: Setting COMx - MODBUS

Description of the MODBUS protocol:

Supported standard

PM55x and PM56x: EIA RS-485

PM57x, PM58x and PM59x: EIA RS-232 / RS-485

Number of connection points

1 client

Max. 1 server with RS-232 interface

Max. 31 servers with RS-485

Protocol MODBUS
Operating mode Client/server
Address Server only
Data transmission control CRC16
Data transmission speed Up to 187.500 baud
Encoding

1 start bit

8 data bits

1 parity bit, (optional) even, odd, mark or space

1 or 2 stop bits

Max. cable length for RS-485 1.200 m at 19.200 baud

If a Processor Module provides more than one serial interface, both interfaces (COM1/COM2) can be operated simultaneously as MODBUS interfaces and can operate as MODBUS server as well as MODBUS client.