Error Codes

Caution

For compatibility reasons, the error codes at output ERNO of the RCOM function blocks are not RCOM specific. To obtain the RCOM error code, 8000 hex has to be subtracted from the original value.

Various errors displayed by numbers can occur when using the RCOM Communication Module. The error number is indicated at output ERNO of the corresponding connection elements.

The errors can be divided into two groups: recoverable errors and fatal errors.

The recoverable errors include all errors which occur during transmission of telegrams (character losses, parity errors etc.). In some cases, the Communication Module attempts retransmission in case of transmission errors. The number of attempts can be specified via the parameter “Retransmissions” in the PLC configuration. Further information can be found in section Basic configuration of CM574-RCOM CM574-RCOM: Module Parameters

In case of recoverable errors, the “RUN” LED flashes cyclic. The LED turns into normal operation mode (“ON”) as soon as the error has been fixed.

Fatal errors

If fatal errors occur, the Communication Module terminates communication with the AC500 CPU and the RCOM partners. Fatal erros are indicated by the “ERR” LED.

A reset is required in order to reactivate the Communication Module, e.g. by switching it off and on again.

Table of error codes

The following table contains all possible error codes (hexadecimal and decimal), the error cause and the type of error (fatal or recoverable error).

Error code Cause
(hex) (dec)
0000 0 No error
0001 1 CPU does not respond (possible cause: missing connection element or CPU stopped)
1001 4097 Event queue full
2001 8193 Initialization error: Incorrect address (parameter NODE)
2002 8194 Initialization error: Incorrect address (parameter NODE)
2005 8197 Initialization error: Incorrect parity
2006 8198 Initialization error: Incorrect duplex mode
2007 8199 Initialization error: Incorrect line stab. Time (TLS)
2008 8200 Initialization error: Incorrect carrier delay
2009 8201 Initialization error: Incorrect character timeout
2010 8208 Initialization error: Incorrect turnaround time
2011 8209 Initialization error: Incorrect retransmissions
2012 8210 Initialization error: Incorrect number of preambles
2015 8213 Initialization error: Incorrect type of modem
2018 8216 Initialization error: Incorrect debug level
3001 12289 No CTS during transmission
3002 12290 Timeout, no response telegram
3003 12291 Telegram error (incorrect length code)
3004 12292 Telegram error (incorrect checksum)
3005 12293 Incorrect slave responding
3006 12294 Telegram error (incorrect response code)
4001 16385 Service not known
4002 16386 Incorrect length entry (input LEN)
4003 16387 Incorrect length entry (input LEN)
4004 16388 Incorrect network number (currently unused)
4005 16389 Incorrect data set number (input ID)
4006 16390 Response telegram does not match service
4007 16391 Slave not normalized
4008 16392 Event queue blocked (not normalized)
4010 16400 Invalid time (connection element RCOM_CLOCK)
4020 16416 Slave responds: “application part not ready” (e.g. EN = FALSE)
4030 16432 Slave responds: “application part not ready” (e.g. EN = FALSE)
5000 20480

Communication Module not initialized (after reset)

Remark: Requires restart of the AC500 PLC (abort and restart of the program

6001 24577 Telephone directory or setup data not found
6002 24578 Incorrect entry in telephone directory or setup data
6003 24579 No telephone modem planned
6004 24580 Modem not yet online (service started without RCOM_DIAL)
6005 24581 Modem already online (repeated RCOM_DIAL without RCOM_HANGUP)
FFFF -1 Internal error (fatal)