Delivery \ Time of CI501-PNIO and CI502-PNIO¶
The PROFINET Communication Module CM579-PNIO supports a communication with up to 128 IO devices. The aimed delivery times raise by a greater upgrade of the system.
The following tables show the different delivery times in dependence of a CM579-PNIO Communication Module and the number of CI50x-PNIO modules.
Note
The basic PROFINET cycle is 1 ms (SendClockFactor = 32). The IO devices ReductionRatio value is 1 and the process update cycle is 1 ms.
Quantity of CI50x-PNIO | Clamp-to-clamp response time of digital IO [ms] | Comment |
---|---|---|
2 | 7.1 | The information regards the “Worst Case” |
16 | 7.1 | |
32 | 13.1 | |
Clamp-to-clamp response time of digital IO depending on the quantity of IO devices in the PROFINET network |
Quantity of CI50x-PNIO | Clamp-to-clamp response time of analog IO [ms] | Comment |
---|---|---|
2 | 14.0 | The information regards the “Worst Case” |
16 | 14.0 | |
32 | 18.0 | |
Clamp-to-clamp response time of analog IO depending on the quantity of IO devices in the PROFINET network |