Configuration¶
Function key  
  main  menu with ETH1 / ETH2 mode:Two separate interfaces (see Switch functionality: Switch Functionality of ETHERNET interfaces ETH1/ETH2
Navigation starts with the Processor Module being in RUN/STOP mode (State 0). By pressing one of the three function keys a certain action is triggered. The result of this action is described in the result columns of the tables.
| State | Description - Main menu 1 | Result on pressing one of the function keys | ||
|---|---|---|---|---|
| 0 | The Processor Module is in RUN/STOP mode. | State 1 is displayed. | Remains in RUN/STOP mode. | Remains in RUN/STOP mode. | 
| 1 | State 2 is displayed. | Return into RUN/STOP mode. | Refers to sub menu 1 | |
| 2 | Change the values with the Count up/Count down function keys.  | 
State 3 is displayed. | Return into RUN/STOP mode. | Shows DONE, your settings are saved. Return into RUN/STOP mode. | 
| 3 | State 4 is displayed. | Return into RUN/STOP mode. | Refers to sub menu 1 | |
| 4 | Change the values with the Count up/Count down function keys.  | 
State 5 is displayed. | Return into RUN/STOP mode. | Shows DONE, your settings are saved. Return into RUN/STOP mode. | 
| 5 | Change the values with the Count up/Count down function keys. See also LEDs, Display and Function Keys on the Front Panel.  | 
State 1 is displayed. | Return into RUN/STOP mode. | Shows DONE, your settings are saved. Return into RUN/STOP mode. | 
Function key  
  main  menu with ETH1 / ETH2 mode: Switch functionality ETH1-ETH2 (see Switch functionality: Switch Functionality of ETHERNET interfaces ETH1/ETH2
Navigation starts with the Processor Module being in RUN/STOP mode (State 0). By pressing one of the three function keys a certain action is triggered. The result of this action is described in the result columns of the tables.
| State | Description - Main menu 2 | Result on pressing one of the function keys | ||
|---|---|---|---|---|
| 0 | The Processor Module is in RUN/STOP mode. | State 1 is displayed. | Remains in RUN/STOP mode. | Remains in RUN/STOP mode. | 
| 1 | State 2 is displayed. | Return into RUN/STOP mode. | Refers to sub menu 1 | |
| 2 | Change the values with the Count up/Count down function keys.  | 
State 3 is displayed. | Return into RUN/STOP mode. | Your settings are saved. State 2 is displayed. | 
| 3 | Change the values with the Count up/Count down function keys. See also LEDs, Display and Function Keys on the Front Panel.  | 
State 1 is displayed. | Return into RUN/STOP mode. | Shows DONE, your settings are saved. Return into RUN/STOP mode. | 
Function key  
  sub  menu IPETH1 or IPETH2; DHCP not active
| State | Description - Submenu 1 | Result on pressing one of the function keys | ||
|---|---|---|---|---|
| 1.1 | IPETH1 or IPETH2  | 
State 2 is displayed. | Return into RUN/STOP mode. | State 1.2 is displayed. | 
| 1.2 | IP Configuration (address, subnet mask, gateway)  | 
State 1.3 is displayed. | Aborts the menu unchanged. Return to State 1.1 | State 3.2 is displayed. | 
| 1.3 | Reset to production data (default settings)  | 
State 1.4 is displayed. | Aborts the menu unchanged. Return to State 1.1 | Activate RESET to default by pressing   Shows DONE, your settings are saved. Return into RUN/STOP mode.  | 
| 1.4 | Activate DHCP Sets a DHCP address.  | 
State 1.2 is displayed. | Aborts the menu unchanged. Return to State 1.1 | Activate DHCP to default by pressing   Shows DONE, your settings are saved. Return into RUN/STOP mode.  | 
Function key  
  sub  menu IPETH1 or IPETH2; DHCP active
| State | Description - Submenu 2 | Result on pressing one of the function keys | ||
|---|---|---|---|---|
| 2.1 | IPETH1 or IPETH2  | 
State 2 is displayed. | Aborts the menu unchanged. Return to State 0. | State 2.2 is displayed. | 
| 2.2 | DHCP active  | 
State 2.3 is displayed. | Aborts the menu unchanged. Return to State 2.1. | – | 
| 2.3 | IP Configuration (address, subnet mask, gateway)  | 
State 2.4 is displayed. | Aborts the menu unchanged. Return to State 2.1. | State 3.2 is displayed. | 
| 2.4 | Reset to production data (default settings)  | 
– | Aborts the menu unchanged. Return to State 2.1. | Activate RESET to default by pressing   Shows DONE, your settings are saved. Return into RUN/STOP mode.  | 
Function key  
  sub  menu STATIC
| State | Description - Submenu 3 | Result on pressing one of the function keys | ||
|---|---|---|---|---|
| 3.1 | IP Configuration (address, subnet mask, gateway)  | 
State 2.4 is displayed. | Aborts the menu unchanged. Return to State 1.1 (sub menu IPETH1 or IPETH2)  | 
State 3.2 is displayed. | 
| 3.2 | IP address A1-A4 
  | 
State 3.3 is displayed. | Aborts the menu unchanged. Return to State 1.1 (sub menu IPETH1 or IPETH2)  | 
Sends changed values to CPU and go to default menue RUN/STOP Displays: DONE New settings stored in CPU. or: FAIL Failed to write new settings to CPU.  | 
| 3.3 | Subnet mask N1-N4 
  | 
State 3.4 is displayed. | Aborts the menu unchanged. Return to State 1.1 (sub menu IPETH1 or IPETH2)  | 
Sends changed values to CPU and go to default menue RUN/STOP Displays: DONE New settings stored in CPU. or: FAIL Failed to write new settings to CPU.  | 
| 3.4 | Gateway G1-G4 
  | 
State 3.2 is displayed again. | Aborts the menu unchanged. Return to State 1.1 (sub menu IPETH1 or IPETH2) Aborts the menu unchanged. Return to State 1.  | 
Sends changed values to CPU and go to default menue RUN/STOP Displays: DONE New settings stored in CPU. or: FAIL Failed to write new settings to CPU.  | 
Function key  
  sub  menu ADR
| State | Description - Submenu 4 | Result on pressing one of the function keys | ||
|---|---|---|---|---|
| 4.1 | State 4.2 is displayed. | Aborts the menu unchanged. Return to State 1  | 
DHCP not active: State 1.2 is displayed DHCP active: State 2.2 is displayed  | 
|
| 4.2 | Change the values with the Count up/Count down function keys starting with current value. 
  | 
State 2.3 is displayed. | Aborts the menu unchanged. Return to State 4.1  | 
Sends changed values to CPU and go to default menue RUN/STOP Displays: DONE New settings stored in CPU. or: FAIL Failed to write new settings to CPU.  | 
| 4.3 | Subnet mask N1-N4 
  | 
State 4.1 is displayed. | Aborts the menu unchanged. Return to State 4.1  | 
Sends changed values to CPU and go to default menue RUN/STOP Displays: DONE New settings stored in CPU. or: FAIL Failed to write new settings to CPU.  | 
  twice.
  Number is blinking if value has changed and is not yet sent to CPU