Information Data Section (Acyclic Data)¶
The information data section can be used to read out common and module specific information.
This section is read only.
Register (hex) | Description | Readable by MODBUS function code | Writeable by MODBUS function code |
---|---|---|---|
0 | Device and FW information CI | 3 | x |
50 | Production data CI | 3 | x |
100 | Device and FW information 1. EXP | 3 | x |
125 | Device and FW information 1. Hot swap terminal unit | 3 *) | x |
150 | Production data 1. EXP | 3 | x |
175 | Production data 1. Hot swap terminal unit | 3 *) | x |
… | … | x | |
A00 | Device and FW information 10. EXP | 3 | x |
A25 | Device and FW information 10. Hot swap terminal unit | 3 *) | x |
A50 | Production data 10. EXP | 3 | x |
A75 | Production data 10. Hot swap terminal unit | 3 *) | x |
D00 | Common device information | 3 | x |
*) supported from CI52x firmware version V3.2.0 (device index F0)
This section can be divided again in two sections:
- The module specific section (containing information for each module CI52x-MODTCP and expansion modules and hot swap terminal units)
- The common device information block