Interfaces for Inputs and OutputsΒΆ
PM57x, PM58x and\ PM59x (AC500)
The following input and output interfaces are available for the AC500 CPUs PM57x, PM58x and PM59x:
No. | Type | Designation | Number of Inputs and Outputs |
---|---|---|---|
1 | I/O bus | Interface for I/O modules | Max. 10 modules with a maximum of 32 channels (IX, QX, IW, QW) per module |
2 | COM1 | CS31 bus master | Max. 31 modules with a maximum of 32 channels per module, address 0-61 |
3 | COM2 | Reserved | RS-232 / RS-485 |
4 | FBP | FieldBusPlug - Slave | Max. 8 modules with 16 IW + 16 QW + 16 IB + 16 QB with modular FBP, depending on fieldbus |
5 | Onboard I/Os | Reserved | Max. 96 bytes Inputs and Outputs |
6 | Line 0 | Internal Communication Module | 4 kB %I0.xx / %Q0.xx each |
7 | Line 1 | Communication Module 1 | 4 kB %I1.xx / %Q1.xx each |
8 | Line 2 | Communication Module 2 | 4 kB %I2.xx / %Q2.xx each |
9 | Line 3 | Communication Module 3 | 4 kB %I3.xx / %Q3.xx each |
10 | Line 4 | Communication Module 4 | 4 kB %I4.xx / %Q4.xx each |
11 | Line 5 | Internal Communication Module ETH3 of PM595-4ETH | 4 kB %I5.xx / %Q5.xx each |
12 | Line 6 | Internal Communication Module ETH4 of PM595-4ETH | 4 kB %I6.xx / %Q6.xx each |
PM55x and PM56x (AC500-eCo)
The following inputs and outputs interfaces are available for the AC500-eCo CPUs PM55x and PM56x:
No. | Type | Designation | Number of Inputs and Outputs |
---|---|---|---|
1 | I/O bus | Interface for I/O modules | Max. 10 I/O modules with a maximum of 32 channels (IX, QX, IW, QW) per module |
2 | COM1 | CS31 bus master | Max. 31 modules with a maximum of 32 channels per module, address 0-61 |
3 | COM2 | Reserved | RS-485 |
4 | Onboard I/O | Onboard I/O | Per module: Option 1: 8DI+6DO Option 2: 8DI+6DO+2AI+1AO |