Interfaces for Inputs and OutputsΒΆ

PM57x, PM58x and\ PM59x (AC500)

The following input and output interfaces are available for the AC500 CPUs PM57x, PM58x and PM59x:

No. Type Designation Number of Inputs and Outputs
1 I/O bus Interface for I/O modules Max. 10 modules with a maximum of 32 channels (IX, QX, IW, QW) per module
2 COM1 CS31 bus master Max. 31 modules with a maximum of 32 channels per module, address 0-61
3 COM2 Reserved RS-232 / RS-485
4 FBP FieldBusPlug - Slave Max. 8 modules with 16 IW + 16 QW + 16 IB + 16 QB with modular FBP, depending on fieldbus
5 Onboard I/Os Reserved Max. 96 bytes Inputs and Outputs
6 Line 0 Internal Communication Module 4 kB %I0.xx / %Q0.xx each
7 Line 1 Communication Module 1 4 kB %I1.xx / %Q1.xx each
8 Line 2 Communication Module 2 4 kB %I2.xx / %Q2.xx each
9 Line 3 Communication Module 3 4 kB %I3.xx / %Q3.xx each
10 Line 4 Communication Module 4 4 kB %I4.xx / %Q4.xx each
11 Line 5 Internal Communication Module ETH3 of PM595-4ETH 4 kB %I5.xx / %Q5.xx each
12 Line 6 Internal Communication Module ETH4 of PM595-4ETH 4 kB %I6.xx / %Q6.xx each

PM55x and PM56x (AC500-eCo)

The following inputs and outputs interfaces are available for the AC500-eCo CPUs PM55x and PM56x:

No. Type Designation Number of Inputs and Outputs
1 I/O bus Interface for I/O modules Max. 10 I/O modules with a maximum of 32 channels (IX, QX, IW, QW) per module
2 COM1 CS31 bus master Max. 31 modules with a maximum of 32 channels per module, address 0-61
3 COM2 Reserved RS-485
4 Onboard I/O Onboard I/O

Per module:

Option 1: 8DI+6DO

Option 2: 8DI+6DO+2AI+1AO