Configuration of the PROFINET® IO Controller

Double-click on CM579_Master (CM579-PNIO-Master) to open the PROFINET® IO Controller parameters in the editor window:

../_images/e5c313cc45ffed0f0a33139000eba54e

The following parameters are available:

Parameter Default Value Meaning

Parameter

(Remark 1 Configuration of the PROFINET® IO Controller)

Identification
IP address 192.168.0.1 Valid IP address IP address of the PROFINET® IO Controller station. IP address
Subnet mask 255.255.255.0 Valid subnet mask Network mask of the PROFINET® IO Controller station. Subnet Mask
Default gateway 0.0.0.0 Valid gateway address Gateway address of the PROFINET® IO Controller station. Default gateway
Station name controller Up to 240 characters Network name of the PROFINET® IO Controller station. Must be a DNS compatible name. Station name
Address settings for devices
First IP address 192.168.0.2 Valid IP address First IP address of the PROFINET® IO Devices. This parameter determines the address range of the PROFINET® IO Devices in combination with parameter Last IP address. First IP address
Last IP address 192.168.0.254 Valid IP address Last IP address of the PROFINET® IO Devices. This parameter determines the address range of the PROFINET® IO Devices in combination with parameter First IP address. Last IP address
Subnet mask 255.255.255.0 Valid subnet mask Network mask of the PROFINET® IO Devices. Default subnet mask
Default gateway 0.0.0.0 Valid gateway Gateway address of the PROFINET® IO Devices. Default gateway address

Remark 1: Tab CM579-PNIO-Master Configuration

The tab-sheet CM579-PNIO-Master Configuration is a generic view of all PROFINET® IO Controller parameters. It is normally hidden and is normally not needed for configuration.

Use this dialog only, if you need to change a parameter, which is not visible in all the other dialogs.

This dialog could be activated with the parameter Show generic device configuration views in the Automation Builder options (Open the Options dialog window with menu item Tools -> Options… the parameter is located under section Device editor).

../_images/e2864f5645ffed5d0a33139000eba54e