Technical Data

The System Data of AC500 and S500 are valid for standard version System Data AC500.

The System Data of AC500-XC are valid for the XC version System Data AC500-XC.

Only additional details are therefore documented below.

Communication module CM592-DP  
Field bus PROFIBUS® DP Master V0 / V1
Transmission rate 9.6 kBit/s to 12 MBit/s
Field bus connector D-SUB, 9-pole, female
Technology Hilscher netX100
Indicators 5 LEDs
Usable CPUs PM57x, PM58x, PM59x PM57x (-y), PM58x (-y) and PM59x (-y)
Usable Terminal Bases All TB5xx TB51x-TB54x
Ingress protection IP20
Current consumption from 24 V DC power supply at the Terminal Base of the CPU Typ. 150 mA
Internal power supply Through the Communication Module interface of the Terminal Base
Number of IO Devices Max. 125
Quantity of input and output data per IO Device 244 byte (respectively for input and output)
Total quantity of input and output data Max. 4096 byte (respectively for input and output)
Bus configuration Done with Automation Builder
Weight Ca. 150 g
Processor Hilscher netX100
Current consumption from 24 VDC power supply at the Terminal Base of the CPU Typ. 150 mA
Internal RAM memory 8 MB
External Flash memory 8 MB

Technical Data of the Interface

Interface socket 9-pole, SUB-D socket
Transmission standard EIA RS-485 acc. to EN 50170, potential-free
Transmission protocol PROFIBUS® DP, 12 Mbaud max.
Transmission rate Baudrate 9.6 kbit/s up to 12.000 kbit/s
Status indication By 5 LEDs

Number of subscribers

(master/slave modules per bus segment)

32 max.
Number of subscribers via repeaters 126 max.