Parameterization¶
Note
You can see the FBP FieldBusPlug Devices in the Internet: http://www.abb.us/product/us/9AAC100124.aspx?productLanguage=us&country=US
During system start-up, the master Communication Module automatically sends parameter data to the slave.
The arrangement of the parameter data is performed by your master configuration software SYCON in connection with the S500 GSD files and in conjunction with the Control Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters into your system configuration.
Module: DC505-FBP as master has the fixed slot number: 0x00
Nr. | Name | Value | Internal value |
Internal value, type |
Default | Min. | Max. | EDS Slot/ Index |
---|---|---|---|---|---|---|---|---|
I/O-Bus master type | Internal | 0 - CPU 1 - FBP |
WORD | 1 0x0001 |
0 | 5 | 0x0001 | |
Minimum bus cycle time [µs] | Internal | 500 | WORD | 500 0x01f4 |
200 | 65535 | 0x0002 | |
Max. failures in succession | Internal | 50 | BYTE | 50 0x32 |
0 | 255 | 0x0003 | |
Error LED / Failsafe function On (+16) | On Off_by_E4 Off_by_E3 |
0 / 16 1 / 17 2 / 18 |
BYTE | 0 0x00 |
0x0004 | |||
1 | I/O Module ID | Internal | 1250 *1) |
Word | 1250 0x04e2 |
0 | 65535 | 0x0005 |
3 | Parameter length | Internal | 5 | Byte | 5-FBP 0x05 |
0 | 255 | 0x0006 |
4 | Check supply | Off on |
0 1 |
Byte | On 0x01 |
0x0007 | ||
5 | Input delay | 0.1 ms 1 ms 8 ms 32 ms |
0 1 2 3 |
Byte | 8 ms 0x02 |
0x0008 | ||
6 | Output short-circuit detection | Off On |
0 1 |
Byte | On 0x01 |
0x0009 | ||
7 | Behaviour of outputs at communication errors | Off Last value Substitute value |
0 1+(n*5) 2+(n*5), n <=2 |
Byte | Off 0x00 |
0x000A | ||
8 | Substitute value at outputs Bit 7 = Output 7 Bit 0 = Output 0 |
0…255 | 0… 0xff |
Byte | 0 0x00 |
0x000B |
*1) With FBP, the value is increased by 1
GSD file: | Ext_User_Prm_Data_Len = Ext_User_Prm_Data_Const(0) = |
14 0x00, 0x01, 0x01,0xf4, 0x32, 0x00, \ 0x04, 0xe3, 0x05, \ 0x01, 0x02, 0x01, 0x00, 0x00; |