Parameterization

Note

You can see the FBP FieldBusPlug Devices in the Internet: http://www.abb.us/product/us/9AAC100124.aspx?productLanguage=us&country=US

During system start-up, the master Communication  Module automatically sends parameter data to the slave.

The arrangement of the parameter data is performed by your master configuration software SYCON in connection with the S500 GSD files and in conjunction with the Control Builder software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters into your system configuration.

Module: DC505-FBP as master has the fixed slot number: 0x00

Nr. Name Value

Internal

value

Internal

value, type

Default Min. Max.

EDS

Slot/

Index

  I/O-Bus master type Internal

0 - CPU

1 - FBP

WORD

1

0x0001

0 5 0x0001
  Minimum bus cycle time [µs] Internal 500 WORD

500

0x01f4

200 65535 0x0002
  Max. failures in succession Internal 50 BYTE

50

0x32

0 255 0x0003
  Error LED / Failsafe function On (+16)

On

Off_by_E4

Off_by_E3

0 / 16

1 / 17

2 / 18

BYTE

0

0x00

    0x0004
1 I/O Module ID Internal

1250

*1)

Word

1250

0x04e2

0 65535 0x0005
3 Parameter length Internal 5 Byte

5-FBP

0x05

0 255 0x0006
4 Check supply

Off

on

0

1

Byte

On

0x01

    0x0007
5 Input delay

0.1 ms

1 ms

8 ms

32 ms

0

1

2

3

Byte

8 ms

0x02

    0x0008
6 Output short-circuit detection

Off

On

0

1

Byte

On

0x01

    0x0009
7 Behaviour of outputs at communication errors

Off

Last value

Substitute value

0

1+(n*5)

2+(n*5),

n <=2

Byte

Off

0x00

    0x000A
8

Substitute value at outputs

Bit 7 = Output 7

Bit 0 = Output 0

0…255

0…

0xff

Byte

0

0x00

    0x000B

*1) With FBP, the value is increased by 1

GSD file:

Ext_User_Prm_Data_Len =

Ext_User_Prm_Data_Const(0) =

14

0x00, 0x01, 0x01,0xf4, 0x32, 0x00, \

0x04, 0xe3, 0x05, \

0x01, 0x02, 0x01, 0x00, 0x00;