Technical Data of the Entire \ Module¶
| Rated supply voltage of the module | 24 V DC (through the FieldBusPlug) | |
| Current consumption of the module | 15 mA (through the FieldBusPlug) | |
| Process voltage UP | ||
| Rated value | 24 V DC (for inputs and outputs) | |
| Max. current loadability for the supply terminals | 10 A | |
| Protection against reversed voltage | Yes | |
| Rated protection fuse at UP | 10 A fast | |
| Electrical isolation | FBP system bus interface from the rest of the module | |
| Inrush current from UP (at power-up) | 0.008 A²s | |
| Current consumption from UP at normal operation / with outputs | 0.005 A + 0.5 A per output | |
| Connections | Terminals 1.8 - 2.8 for +24 V (UP) and 1.9 - 2.9 for 0 V (ZP) | |
| Max. power dissipation within the module | 6 W (outputs unloaded) | |
| Number of digital inputs | 8 | |
| Number of configurable digital inputs/outputs | 8 | |
| Reference potential for all digital inputs and outputs | Minus pole of the supply voltage, signal name ZP | |
| Address setting | With 2 rotary switches on the front panel | |
| Diagnosis | Chapter FBP Interface Module DC505-FBP with Digital Inputs and Outputs | |
| Operating and error displays | 23 LEDs altogether | |
| Weight (without Terminal Unit) | ca. 125 g | |
| Mounting position | Horizontal Or vertical with derating (output load reduced to 50 % at 40 °C per group) |
|
| Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. | |
Note
All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.