Technical Data of the Digital \ OutputsΒΆ

Number of channels per module 16 outputs (with transistors)
Distribution of the channels into groups 1 group of 16 channels
Connection of the channels  
  DO0 to DO7 Terminals 1.0 to 1.7
  DO8 to DO15 Terminals 2.0 to 2.7
Indication of the output signals 1 yellow LED per channel, the LED is ON if the output signal is high (signal 1)
Reference potential for all outputs Terminals 1.9, 2.9, 3.9 and 4.9 (minus pole of the process supply voltage, signal name ZP)
Common power supply voltage For all outputs: terminals 1.8, 2.8, 3.8 and 4.8 (plus pole of the process supply voltage, signal name UP)
Output voltage for signal 1 UP (-0.8 V)
Output delay (0->1 or 1->0) On request
Output current  
  Rated value, per channel 500 mA at UP = 24 V
  Maximum value (channels O0 to O15) 4 A
Leakage current with signal 0 < 0.5 mA
Rated protection fuse on UP 10 A fast
Demagnetization when inductive loads are switched off With varistors integrated in the module (see figure below)
Switching frequency  
  With resistive load On request
  With inductive loads Max. 0.5 Hz
  With lamp loads Max. 11 Hz with max. 5 W
Short-circuit proof / overload proof Yes
Overload message (I > 0.7 A) Yes, after ca. 100 ms
Output current limitation Yes, automatic reactivation after short-circuit/overload
Resistance to feedback against 24V signals Yes
Max. cable length  
  Shielded 1000 m
  Unshielded 600 m