Parameterization¶
The arrangement of the parameter data is depending on the firmware version installed inside the CPUs and Bus Modules:
Firmware version | Mounting position | Configuration |
---|---|---|
Firmware version < V2.0.0 |
|
The arrangement of the parameter data is performed by PLC-Configuration inside Control Builder software. |
|
The arrangement of the parameter data is performed by your master configuration software SYCON.net in connection with the S500 GSD files and in conjunction with the Control Builder software. | |
Firmware version > V2.0.0 |
|
The arrangement of the parameter data is performed by Control Builder Plus software. |
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configuration.
Module slot address: Y = 1…7
Name | Value | Internal Value |
Internal Value, type |
Default | EDS Slot / Index |
---|---|---|---|---|---|
Module ID *1) | Internal | 1815 | WORD | 1815 | 0x0Y01 |
Ignore module | Internal | Yes No |
BYTE | No | |
Parameter length | Internal | 8 | BYTE | 8 | 0xY02 |
Check supply | off | 0 | BYTE | 0xY03 | |
on | 1 | 1 | |||
Fast counter *3) | 0 : 10 *2) |
0 : 10 |
BYTE | 0 | not for FBP |
Behaviour outputs at comm. error *5) | Off Last value Last value 5 sec Last value 10 sec Substitute value Substitute value 5 sec Substitute value 10 sec |
0 1 6 11 2 7 12 |
BYTE | Off 0x00 |
0x0Y07 |
*1) With a faulty ID, the Modules reports a “parameter error” and does not perform cyclic process data transmission
*2)Counter operating modes Fast Counter, see description of the Fast Counter Fast Counter
*3) With CS31 without the parameter “Fast Counter”
Note
The Fast Counter of the module does not work if the module is connected to a CS31 Bus Module.
*5) The parameter Behaviour outputs at comm. error is only analyzed if the Failsafe-mode is ON.
*2) | Setting | Meaning |
---|---|---|
On | Error-LED lights up at errors of all error classes, Failsafe-mode off | |
Off by E4 | Error LED lights up at errors of error classes E1, E2 and E3, Failsafe-mode off | |
Off by E3 | Error LED lights up at errors of error classes E1 and E2, Failsafe-mode off | |
On +Failsafe | Error-LED lights up at errors of all error classes, Failsafe-mode on* | |
Off by E4 + Failsafe | Error LED lights up at errors of error classes E1, E2 and E3, Failsafe-mode on* | |
Off by E3 + Failsafe | Error LED lights up at errors of error classes E1 and E2, Failsafe-mode on* |